SK-2224 Basic Operating Instructions P/N 151064
These instructions must be framed and displayed next to the SK-2224 panel in accordance 
with NFPA 72 fire code for Local Fire Alarm System.
 
LED (Color)
Function
AC (green)
ON = Good AC
OFF = Low AC trouble condition and it was acknowledged
FLASHING = Unacknowledged AC Low trouble condition
GENERAL TROUBLE 
(yellow)
ON = System trouble
OFF = System OK
FLASHING = At least one serial device is in trouble
DOUBLE FLASHING = Two types of serial devices are in trouble.
WALK TEST (yellow)
ON = Walk test is in progress
OFF = Walk test is off.
FLASHING = Walk test is on and at least one zone is not ready
GND FAULT (yellow)
ON = Ground fault condition exists and was acknowledged
OFF = No fault
FLASHING = A ground fault condition detected
LOW BATTERY (yellow)
ON = Battery low condition that has been acknowledged
OFF = Good battery condition
FLASHING = Battery low condition
ZONE 1 
and
ZONE 2
ALARM (red)
ON = Zone in alarm which has been acknowledged
OFF = No Alarm
FLASHING = Zone in alarm has not yet been acknowledged.
SUPERVISORY 
(yellow)
ON = Zone has a supervisory condition (self-restoring condition)
OFF = No supervisory condition exists.
FLASHING = supervisory trouble detected on that zone.
TROUBLE 
(yellow)
ON = Zone has a trouble condition which has been acknowledged
OFF = No zone trouble
FLASHING = Zone has a trouble condition
DOUBLE FLASHING = Zone was disabled
CLEAN ME FLASHING = 
Indicates that the smoke detector needs cleaning (LED is on long  and  
Off for a short time period)
NAC 1 
and
NAC 2
ACTIVE (yellow) ON = NAC is active during an alarm
OFF = NAC is not active during alarm
TROUBLE 
(yellow)
ON = NAC has a trouble condition and was acknowledged
OFF = No trouble condition
FLASHING = NAC is in trouble
DOUBLE FLASHING = Circuit was disabled
SYSTEM SILENCED 
(yellow)
ON = System audible output has been silenced
OFF = Nothing silenced
FLASHING = Partially silenced
Operation
Keystrokes
Disable notification appliance circuit. 
To re-enable the circuit, press [NAC 
DISABLE] again.
Press the appropriate [NAC DISABLE] key. The NAC circuit will be disabled and the corresponding 
TROUBLE LED will Double Flash. This function is not available during an alarm condition.
Disable a zone
To re-enable the circuit, press [ZONE 
DISABLE] again.
Press the appropriate [ZONE DISABLE] key. The zone will be disabled and the corresponding TROUBLE 
LED will Double Flash. This function is not available during an alarm or supervisory condition.
Begin Walk Test
Press [WALK TEST]. Walk Test LED turns on. 
Note:
Walk test will not activate if the control panel has a trouble, alarm, or supervisory condition.
End Walk Test
Press [WALK TEST].
NOTE: The Walk Test feature is not operational during an alarm, supervisory or any system trouble 
condition.The test ends automatically after 10 minutes of no system activity.
Acknowledge condition (alarm, supervisory, 
trouble) 
Press [ACK]. The corresponding LED will change from blinking to steady for the duration of the condition.
Silence Panel
Press [SILENCE]. This will silence the on-board PZT and all active NAC circuits that have been configured as 
"silenceable". 
Perform system reset
Press [RESET]. Resets alarms, supervisories, troubles and all LEDs.
Manual Dialer Test.
Press the [ACK] and [ SILENCE] buttons at the same time.
Dialer Reset.
Press the [RESET] and [WALK TEST] buttons at the same time.