UBC10.241, UBC10.241-N1 
 
  USeries 
24V, 10A, DC-UPS 
 
 
May. 2008 / Rev. 1.1  DS-UBC10.241-EN 
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time  
unless otherwise noted. It is assumed that the input power source can deliver a sufficient output current. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
15/23 
 
18.  E
NVIRONMENT
 
 
  Operational temperature 
0°C to +40°C (32°F to 104°F) 
Full output power 
  Storage temperature 
-20°C to +50°C  (-4°F to 122°F) 
Storage and transportation 
 
Humidity 
5 to 95% r.H. 
IEC 60068-2-30 
Do not energize while condensation is present 
  Vibration sinusoidal 
2-17.8Hz: ±1.6mm; 17.8-500Hz: 1g *)  IEC 60068-2-6 
  Shock 
15g 6ms, 10g 11ms *) 
IEC 60068-2-27 
  Altitude 
0 to 6000m 
Approvals apply only up to 2000m 
  Over-voltage category 
III 
EN 50178 
   
II 
EN 50178   above 2000m altitude 
  Degree of pollution 
EN 50178, not conductive 
*)   Use wall mounting accessory for higher values. 
 
 
Fig. 18-1   Normal Mode: Output current vs. 
ambient temperature 
 
Fig. 18-2   Buffer Mode: Output current vs. 
ambient temperature 
 
Allowable Output 
Current in Normal Mode
0
0
10
20
60°C
2.5
5
7.5
10
12.5
15A
continuous
Ambient Temperature
30
40
50
 
 
Allowable Output 
Current in Buffer Mode
0
0
10
20
60°C
2.5
5
7.5
10
12.5
15A
continuous
Ambient Temperature
for typ. 5s
30
40
50
 
The ambient temperature is defined 2cm below the unit. 
 
 
19.  P
ROTECTION 
F
EATURES
 
 
 Output 
protection 
Electronically protected against overload, no-load and short-circuits 
  Output over-voltage protection 
in buffer mode 
typ. 32Vdc 
max. 35Vdc 
In case of an internal defect, a redundant circuitry 
limits the maximum output voltage. The output 
automatically shuts-down and makes restart attempts. 
  Degree of protection 
IP20 
EN/IEC 60529 
  Penetration protection 
> 3.5mm 
E.g. screws, small parts 
  Reverse battery polarity protection 
yes 
Max. –35Vdc;  
  Wrong battery voltage protection 
yes 
Max. +35Vdc  (e.g. 24V battery instead of 12V battery) 
  Battery deep discharge protection 
yes 
The limit is battery current dependent 
  Over temperature protection 
yes 
Output shut-down with automatic restart 
 Input 
over-voltage 
protection 
yes 
Max. 35Vdc, no harm or defect of the unit 
 Internal 
input 
fuse 
25A, 
blade type 
No user accessible part, no service part