Техническое Руководство для Puls UBC10.241 DIN-Rail UPS

Скачать
Страница из 23
 
 
 
UBC10.241, UBC10.241-N1 
 
  USeries 
24V, 10A, DC-UPS 
 
 
May. 2008 / Rev. 1.1  DS-UBC10.241-EN 
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time  
unless otherwise noted. It is assumed that the input power source can deliver a sufficient output current. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
19/23 
 
26.  R
EPLACEMENT OF THE BATTERY
 
 
The integrated battery should be replaced on a periodic basis, see chapter 28.1 for additional information.  
The replacement should be done by qualified personnel trained on battery handling. 
Caution! The terminals on the battery are always alive, therefore do not place items or tools on the battery! 
How to replace the battery: 
 
 
 
 
 
 
 
 
  Step 1:  
Remove 
the fuse 
before 
working on 
the unit.  
Step 2:  
Loosen the 
captive cover 
screw. 
Step 3: 
Remove the 
battery-cover. 
 
Step 4: 
 
Disconnect the cables 
from the battery 
terminals.  
 
Step 5: 
 
Remove the 
battery by pulling 
on the strap.  
 
 
Step 6:  Install the new battery.  
Step 7:  Connect the red cable (+) to the red positive (+) terminal of the battery. 
Step 8:  Connect the black cable (-) to the black negative (-) terminal of the battery. 
Step 9:  Close the cover. 
Step 10:  Tighten the screw. 
Step 11:  Plug-in the fuse. 
 
Disposal of batteries 
Batteries marked with the recycling symbol should be recycled through a competent agency.  
 
 
 
Replacement battery 
See chapter 27 for information on the UZB12.051 or you can use a battery which meets the following requirements: 
 
Battery type 
nom. 
12V, 4 to 6Ah 
VRLA lead-acid maintenance free battery  
 
Design life 
min. 
3 to 5 years 
According to EUROBAT guideline 
 
Dimensions  
nom. 
70x106x90mm 
WxHxD  *) 
 
Pole connection 
 
6.35mm/ 0.25Inch 
Blade type; Fast-on 
 
Approvals 
 
UL, VdS 
For applications which require UL or VdS 
 
Allowed discharge current 
min. 
29A 
Continuous 
*) 
Max. case height of 102mm