UBC10.241, UBC10.241-N1 
 
  USeries 
24V, 10A, DC-UPS 
 
 
May. 2008 / Rev. 1.1  DS-UBC10.241-EN 
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time  
unless otherwise noted. It is assumed that the input power source can deliver a sufficient output current. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
7/23 
 
9.  B
UFFER 
T
IME
 
 
The buffer time depends on the capacity and performance of the battery as well as the load current. The diagram 
below shows the typical buffer times of the standard battery. 
 
  Buffer time with 5Ah high-current battery 
min. 
13’24’’ 
At 5A output current  *) 
   
min. 
4’54’’ 
At 10A output current  *) 
   
typ. 
16’15’’ 
At 5A output current, see Fig. 9-1 **) 
   
typ. 
6’15’’ 
At 10A output current, see Fig. 9-1 **) 
*)   Minimum value includes 20% aging and requires a fully charged (min. 24h) battery. 
**)  Typical value includes 10% aging and requires a fully charged (min. 24h) battery. 
 
 
 
Fig. 9-1   
Buffer time vs. output current with a 5Ah high current battery
 
 
Buffer Current 
0
5
15
2
4
6
8
10A
20
10
25 30 35
45 50
40
55 60 65 70 75 80 85
Buffer Time (Minutes) 
UZB12.051
90
    Min.
12V 5Ah high current battery