All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
16/20 
 
25. A
PPLICATION 
N
OTES
 
25.1. P
EAK 
C
URRENT 
C
APABILITY
 
Solenoids, contactors and pneumatic modules often have a steady state coil and a pick-up coil. The inrush current 
demand of the pick-up coil is several times higher than the steady state current and usually exceeds the nominal 
output current (including the PowerBoost) The same situation applies, when starting a capacitive load. 
Branch circuits are often protected with circuit breakers or fuses. In case of a short or an overload in the branch 
circuit, the fuse needs a certain amount of over-current to trip or to blow. The peak current capability ensures the 
safe operation of subsequent circuit breakers. 
Assuming the input voltage is turned on before such an event, the built-in large sized output capacitors inside the 
power supply can deliver extra current. Discharging this capacitor causes a voltage dip on the output. The following 
two examples show typical voltage dips: 
Fig. 25-1   Peak load 10A for 50ms, typ. 
 
Fig. 25-2   Peak load 25A for 5ms, typ. 
10ms/DIV
Output
Voltage
Output
Current
48V
0A
10A
38V
 
 
1ms/DIV
Output
Voltage
Output
Current
48V
0A
25A
28V
 
Peak load 10A (resistive) for 50ms 
Output voltage dips from 48V to 38V. 
 
Peak load 25A (resistive) for 5ms 
Output voltage dips from 48V to 28V. 
 
25.2. C
HARGING OF 
B
ATTERIES
 
The power supply shall not be used to charge batteries. Choose Q-Series for charging batteries.