22.9.  S
ERIES 
O
PERATION
 
Power supplies of the exact same type can be connected in series for higher 
output voltages. It is possible to connect as many units in series as needed, 
providing the sum of the output voltage does not exceed 150Vdc. Voltages 
with a potential above 60Vdc are not SELV any more and can be dangerous. 
Such voltages must be installed with a protection against touching. Earthing of 
the output is required when the sum of the output voltage is above 60Vdc. 
Avoid return voltage (e.g. from a decelerating motor or battery) which is 
applied to the output terminals. Keep an installation clearance of 15mm (left / 
right) between two power supplies and avoid installing the power supplies on 
top of each other. Do not use power supplies in series in mounting 
orientations other than the standard mounting orientation (input terminals on the bottom and output terminals on 
top of the unit). Be ware that leakage current, EMI, inrush current and harmonics will increase when using multiple 
power supplies series. 
Earth
Unit A
AC
DC
Unit B
AC
DC
-
+
-
+
Load
+
-
22.10. O
PERATION ON 
T
WO 
P
HASES
 
2
40V 
+10%
 max.
Fuse
L2
L1
L3
L
N
PE
Power Supply
AC
DC
internal
fuse
The power supply can also be used on two-phases of a three-phase-system. 
A phase-to-phase connection is allowed as long as the supplying voltage is 
below 240V
+10%
. Use a fuse or a circuit breaker to protect the N input. The 
N input is not internally protected and is in this case connected to a hot 
wire. Appropriate fuses or circuit breakers are specified in section 22.4 
“External Input Protection”. 
 
22.11. U
SE 
W
ITHOUT 
PE
 ON THE 
I
NPUT
 
From a safety standpoint, the unit is internally designed according to the requirements for Protection Class 1 and 2. 
Please contact PULS if you do not plan to use the PE terminal. A different marking of the front foil is then required.  
Grounding of the input is beneficial for a high EMI immunity: Symmetrical spikes or fast transients on the input side 
can be conducted directly to earth by the built-in filter capacitors. The magnitude of such spikes or fast transients on 
the output side caused by the input is much smaller compared to not connecting this terminal to ground. 
 
 
Fig. 22-5   Earthed input 
 
Fig. 22-6   Not earthed input 
 
Surge
Y
X
L
N
Ground
Power Supply
+
-
 
 
Surge
X
L
N
Power Supply
+
-
24V
Spike
Mar. 2013 / Rev. 1.2  DS--ML60.121-EN 