Техническое Руководство для Cisco CATALYST 6509E 9 SLOT 15U CHASSIS NO POWER SUPPLY NO FAN TRAY

Скачать
Страница из 336
A-24
Catalyst 6500 Series Switches Installation Guide
OL-5781-04
Appendix A      Power Supply Specifications
  2500 W AC-Input and DC-Input Power Supplies
Branch circuit requirement (AC-input)
Each chassis power supply should have its own 
dedicated, fused-branch circuit:
For North America—20 A
For International—Circuits sized to local and 
national codes
All AC power supply inputs are fully isolated.
Source AC can be out of phase between 
multiple power supplies in the same chassis, 
which means that PS1 can be operating from 
phase A and PS2 can be operating from 
phase B.
Source AC can be out of phase between AC 
inputs on power supplies that are equipped 
with multiple AC inputs, which means that 
power cord 1 can be plugged into phase A and 
power cord 2 can be plugged into phase B.
AC-input frequency
50/60 Hz (nominal) (±3% for full range)
Power supply output capacity
1300 W maximum (100–120 VAC)
2500 W maximum (200–240 VAC)
2500 W maximum (–48 to –60 VDC)
System power dissipation
3520 W (total input power) or 3.6 KVA (high-line 
operation)
DC-input voltage
–48 VDC to –60 VDC continuous
DC-input current
80 A @ –40.5 VDC
70 A @ –48 VDC
55 A @ –60 VDC
Power supply output (AC supply)
100/120 VAC operation
15.5 A @ +3.3 V
5 A  @  +5 V
10 A @ +12 V
27.5 A @ +42 V
200/240 VAC operation
15 A @ +3.3 V
5 A  @  +5 V
10 A @ +12 V
55.5 A @ +42 V
Table A-11 2500 W Power Supply Specifications (continued)
Specification
Description