Справочник Пользователя для EnOcean GmbH PTM33XC

Скачать
Страница из 20
USER MANUAL V0.8 
© 2009 EnOcean  |  www.enocean.com 
PTM 33x / 33xC User Manual V0.8  |  Page 7/20 
 
 
PTM 33X / 33XC 
2.2  Pin out 
 
 
2.3  Pin Description and operational characteristics 
 
Symbol 
Function 
Characteristics 
GND 
Ground connection 
Must be connected to GND 
V+ 
For test purposes only 
Do not connect 
B0 
O-Button Rocker B 
Digital input, leave open or connect to GND 
Internal pull-up 
B1 
I-Button Rocker B 
Digital input, leave open or connect to GND 
Internal pull-up 
A0 
O-Button Rocker A 
Digital input, leave open or connect to GND 
Internal pull-up 
A1 
I-Button Rocker A 
Digital input, leave open or connect to GND 
Internal pull-up 
CFG 
Activate VOFF comparator 
when connected to GND 
Must be connected to GND when used with 
equivalent energy pulse instead of ECO 200 
Internal pull-up 
AC1 
Input for ECO 200 
ECO 200 or equivalent energy pulse  
AC2 
Input for ECO 200 
ECO 200 or equivalent energy pulse  
RF_WHIP  RF output 
Output for whip antenna 
RF_50 
RF output 
50 Ohm output for external antenna 
T1-9 
Configuration Interface 
See 2.4 
 
 
1
2
3
4
5
6
7
8
11
10
9
12
13
14
15
16
GND
CFG
B0
GND
B1
A0
GND
A1
AC1
AC2
GND
V+
GND
RF_50
GND
RF_WHIP
AC1
AC1
AC2
AC2
On back side of PCB
T4
T3
T8
T6
T5
T9
T7
T1
T2