Справочник Пользователя для EnOcean GmbH STM300C

Скачать
Страница из 46
USER MANUAL V0.82 
© 2010 EnOcean  |  www.enocean.com 
TCM 300 / 300C / 320 / 320C User Manual V0.82  |  Page 37/43 
 
 
TCM 300 / 300C / 320 / 320C 
LENGTH 
(5 bit) 
Number of octets following the header octet (11 dec) 
ORG 
(8 bit) 
Type of telegram (see detailed description below) 
DATA_BYTE 0..3  (8 bit each)  
Data bytes 0..3 (see detailed description below) 
ID_BYTE 0..3 
(8 bit each)  
32-bit transmitter ID
3
 
 
 
For transmission of unique ID enter 0x00000000 
STATUS (8 
bit)  Status field (see detailed description below) 
CHECKSUM 
(8 bit) 
Checksum (Last LSB from addition of all octets except  
  sync 
bytes 
and 
checksum) 
A.2.2  Detailed description of ORG field 
 
ORG field  
(hex) 
Acronym 
Description 
0x05 
RPS 
Repeated Switch 
Telegram from a PTM switch module received  
(e.g. PTM 100 or PTM 200) 
0x06 
1BS 
1 Byte Sensor
 
1 byte data telegram from a STM sensor mod-
ule (e.g. STM 250) 
0x07 
4BS 
4 Byte Sensor
 
4 byte data telegram from a STM sensor mod-
ule (e.g. STM 100) 
0x08 
HRC 
Hand Remote Control
 
Telegram from a CTM module received 
0xC5 
SYS_EX 
System Extended
 
Remote Management Telegrams  
(see separate specification) 
 
 
Please note that 6DT and MDA telegrams, which were available in TCM1xx / 
TCM200C are no longer supported! 
 
 
A.2.3  Detailed description of STATUS field 
 
If ORG = 5 (Telegram from a PTM switch module): 
 
7                                                                0 
Reserved T21  NU 
RP_COUNTER 
 
Reserved 
(2 bit)  
For future use 
T21 (1 
bit) 
T21=0 
Æ PTM switch module of type 1,  
  
T21=1 
Æ PTM switch module of type 2 
NU (1 
bit) 
NU=1 
Æ N-message, NU=0 Æ U-message. 
RP_COUNTER 
(4 bit) =0..15  Repeater level: 0 is original message (not repeated) 
 
 
IMPORTANT NOTE FOR SYSTEMS USING AN ENOCEAN RADIO REPEATER:  
Within toggle switch applications using the serial receiver mode in combination 
with a separate repeater, please ensure that no serial command interpretation 
error may occur at the connected control unit. A toggle signal means that the 
same telegram is sent for switching something  on  and  off.  If  e.g.  the  light  is 
switched on receiving the I-button telegram from a PTM 200C, the repeated tele-
                                          
3
 This module allows using a unique ID or one of 128 IDs starting from BaseID. See  A.3.1.