Справочник Пользователя для EnOcean GmbH STM300C
USER MANUAL V0.82
© 2010 EnOcean | www.enocean.com
TCM 300 / 300C / 320 / 320C User Manual V0.82 | Page 37/43
TCM 300 / 300C / 320 / 320C
LENGTH
(5 bit)
Number of octets following the header octet (11 dec)
ORG
(8 bit)
Type of telegram (see detailed description below)
DATA_BYTE 0..3 (8 bit each)
Data bytes 0..3 (see detailed description below)
ID_BYTE 0..3
(8 bit each)
32-bit transmitter ID
3
For transmission of unique ID enter 0x00000000
STATUS (8
bit) Status field (see detailed description below)
CHECKSUM
(8 bit)
Checksum (Last LSB from addition of all octets except
sync
bytes
and
checksum)
A.2.2 Detailed description of ORG field
ORG field
(hex)
Acronym
Description
0x05
RPS
Repeated Switch
Telegram from a PTM switch module received
(e.g. PTM 100 or PTM 200)
0x06
1BS
1 Byte Sensor
1 byte data telegram from a STM sensor mod-
ule (e.g. STM 250)
0x07
4BS
4 Byte Sensor
4 byte data telegram from a STM sensor mod-
ule (e.g. STM 100)
0x08
HRC
Hand Remote Control
Telegram from a CTM module received
0xC5
SYS_EX
System Extended
Remote Management Telegrams
(see separate specification)
Please note that 6DT and MDA telegrams, which were available in TCM1xx /
TCM200C are no longer supported!
A.2.3 Detailed description of STATUS field
If ORG = 5 (Telegram from a PTM switch module):
7 0
Reserved T21 NU
RP_COUNTER
Reserved
(2 bit)
For future use
T21 (1
bit)
T21=0
Æ PTM switch module of type 1,
T21=1
Æ PTM switch module of type 2
NU (1
bit)
NU=1
Æ N-message, NU=0 Æ U-message.
RP_COUNTER
(4 bit) =0..15 Repeater level: 0 is original message (not repeated)
IMPORTANT NOTE FOR SYSTEMS USING AN ENOCEAN RADIO REPEATER:
Within toggle switch applications using the serial receiver mode in combination
Within toggle switch applications using the serial receiver mode in combination
with a separate repeater, please ensure that no serial command interpretation
error may occur at the connected control unit. A toggle signal means that the
error may occur at the connected control unit. A toggle signal means that the
same telegram is sent for switching something on and off. If e.g. the light is
switched on receiving the I-button telegram from a PTM 200C, the repeated tele-
switched on receiving the I-button telegram from a PTM 200C, the repeated tele-
3
This module allows using a unique ID or one of 128 IDs starting from BaseID. See A.3.1.