A.3 Command telegrams and messages
A.3.1 ID Range commands
Every TCM 300 supports a unique 32 bit ID and in addition a range of 128 IDs starting at
Every TCM 300 supports a unique 32 bit ID and in addition a range of 128 IDs starting at
an BaseID address. At production, every TCM 300 is programmed with a unique ID and a
BaseID address. The BaseID number can be read via the serial interface. In order to allow a
BaseID address. The BaseID number can be read via the serial interface. In order to allow a
replacement of one unit with another unit (without having to go through the learning pro-
cedure with every receiver), the ID range can be changed via the serial interface.
cedure with every receiver), the ID range can be changed via the serial interface.
The allowed ID range is from 0xFF800000 to 0xFFFFFFFF.
In order to prevent misuse, this feature can only be used 10 times!
In order to prevent misuse, this feature can only be used 10 times!
Please note: The unique ID cannot be changed.
Command (TCT)
Response (RMT)
SET_BASEID
OK, ERR, ERR_IDRANGE
RD_BASEID
INF_BASEID
A.3.2 Receiver sensitivity commands
The receiver sensitivity can be changed by the following commands. In LOW sensitivity
mode, only transmitters in the vicinity of the module are received.
mode, only transmitters in the vicinity of the module are received.
Command (TCT)
Response (RMT)
SET_RX_SENSITIVITY
OK
RD_RX_SENSITIVITY
INF_RX_SENSITIVITY
A.3.3 Reset command
Command (TCT)
Response (RMT)
RESET
A.3.4 SW Version
Command (TCT)
Response (RMT)
RD_SW_VER
INF_SW_VER
A.3.5 Error messages
Error Messages (RMT)
ERR
ERR_TX_IDRANGE
ERR_IDRANGE
ERR_SYNTAX
ERR_TX_IDRANGE
ERR_IDRANGE
ERR_SYNTAX