Справочник Пользователя для Simplex Time Recorder Company 31032021330

Скачать
Страница из 12
P/N 330.MAN Rev. 1.0  
 2006 Commercial Wireless Systems International, LLC 
1
  
Fire Transmitter Model 330  
Description: 
The model 330 fire transmitter is a UL864 listed device specifically designed for connection 
to a normally open dry contact output. The input  is  selectable for two  types  of supervised 
wiring configurations referred to as Style 1 or Style 2 in this manual. The transmitter is fully 
supervised for tamper, low battery, RF signal integrity and wiring faults. The transmitter is 
powered by a single 3 volt lithium battery as  listed under the specifications section of this 
manual  and  the  label  on  the  product.  The  model  330  is  intended  to  be  used  with 
Commercial Wireless Systems International, LLC Model CP-3000 Fire Alarm Control Panel. 
Refer  to  the  CP-3000  FACP  installation  instructions,  part  number  3000.MAN  Rev.  1  for 
additional details.  
Programming: 
The 330 must be enrolled into the CP-3000 control panel before installing the device. The 
Model 330 will not report Alarms, Supervisory or trouble signals unless it is enrolled 
into  the  CP-3000  control  panel.  
Enrollment  must  be  performed  while  in  front  of  the  CP-
3000  FACP.  Place  the  CP-3000  FACP  in  enrollment  mode  then  install  the  battery  in  the 
model  330  transmitter  observing  polarity  marked  on  the  battery  holder.  The  model  330 
serial  number  will  be  displayed  on  the  CP-3000  FACP  along  with  programming  options. 
Refer to the CP-3000 control panel installation instructions for further details on enrollment 
and  transmitter  programming  options.  After  the  model  330  is  enrolled,  remove  the  battery 
and reinstall it only at the transmitters mounting location.  
Installation: 
Select  an  accessible  location  that  is  not  prone  to  tampering  or  accidental  damage  The 
mounting surface should be relatively flat and capable of accepting screws or anchors. The 
330 is to be installed in an indoor dry location. Exposure to weather or corrosive conditions 
may damage the unit. It must be mounted on a vertical surface so that the CWSI label can 
be  read  correctly.  Perform  the  signal  test  described  in  this  manual  prior  to  and  after 
permanently mounting the unit
. An 18 gage copper wire pair should be used to connect 
the  330  to  the  dry  contacts  to  be  monitored.  Wire  runs  should  be  as  short  as  possible, 
contained within one room and not routed near fluorescent lighting or equipment generating 
electrical  noise  such  as  generators,  air  conditioners,  etc.  The  wires  should  enter  the  330 
through the hole  provided near the screw terminal  block. Under no circumstances  are the 
wires to be run near or draped over the printed 330 printed circuit board. Style 1 or Style 2 
wiring  can  be  selected  with  SW2  on  the  board.  Refer  to  figure  2  for  proper  wiring 
connection. When Style 2 wiring is selected, the Model TR-3 EOL resistor provided must be 
connected  either  as  recommended  by  the  manufacturer  of  the  device  being  monitored  or 
directly  across  the  dry  contact  terminals  of  the  of  the  monitored  device.  Multiple  sets  of 
contacts  on  the  monitored  equipment  may  be  wired  in  parallel  and  connected  to  a  single 
330.  Caution:  only  one  monitored  device  may  be  connected  to  a  single  Model  330.
  
After  connecting  the  wires  to  the  terminal  block,  install  the  battery,  mount  the  enclosure 
back  on  the  wall  using  the  keyholes  then  push  the  front  portion  of  the  enclosure  onto  the 
back until the case snaps closed. Be careful not to bend the transmitter’s antenna. Perform 
the Signal Test and Alarm Test as outlined in this manual.  
P/N 330.MAN Rev. 1.0  
 2006 Commercial Wireless Systems International, LLC 
Cautions: 
1. Make sure the battery is firmly installed in the battery clip. 
2. The unit must be secured tightly to the wall, so as to not be dislodged. 
3.  Test  the  unit  after  any  service  or  battery  change  or  as  often  as  local  or  national  codes 
dictate.   
Following the codes: 
The Model 330 must be installed and maintained in accordance with the National Fire 
Protection Association’s Standards (NFPA), the National Electrical Code and all local 
fire  and  electrical  requirements.  When  connecting  to  other  equipment,  follow  the 
instructions and recommendations of that manufacturer. 
 
Alarm Operation: 
When the wires of the model 330 are shorted:  
1. An initial alarm signal is transmitted. 
2. A 30 second delay occurs. If during this delay the alarm condition is reset and the alarm 
cycle is ended. 
3. A continued alarm condition causes a repeat alarm transmission. 
4. Another 30 second delay as in step 2 occurs. 
5. A continued alarm condition causes a repeat alarm transmission. 
6. Step 5 repeats at 60 second intervals until reset.  
LED: The LED will flash when any signal is sent from the transmitter.  
Alarm Test: 
Before  testing,  notify  the  proper  authorities  that  maintenance  is  being  performed  and  the 
system will be temporarily out of service. Activate the dry contact output being monitored by 
the Model 330 transmitter or manually short the wires to simulate dry contact closure. Verify 
an alarm is received at the control panel.  
Signal Test: 
The test must be performed while the transmitter is held in its intended mounting location. 
Initiate  the  test  by  placing  a  strong  magnet  along  the  upper  right  side  of  the  transmitter 
case  (figure  1).  The  model  330  piezo  sounder  will  beep  twice  if  the  transmitter  is  located 
within  acceptable  reception  range  of  a  repeater  or  CP-3000  FACP.  If  two  beeps  are  not 
heard  within  5  seconds  of  initiating  the  signal  test  then  relocate  the  model  310  mounting 
position closer to the nearest repeater or control panel and perform the test again. Continue 
this procedure until 2 beeps are achieved. Do not mount the transmitter unless 2 beeps are 
heard  when  performing  the  signal  test.  This  test  must  be  performed  before  and  after 
transmitter  installation.  Note:  A  CWSI  model  AR-3  repeater  or  Control  Panel  must  be 
installed and turned on before running this test.             
Low battery: 
The  battery  voltage  is  periodically  tested  under  load.  In  the  event  that  a  low  battery  is 
detected, a low battery signal will be sent immediately and repeated every 90 seconds for a 
minimum  of  seven  days.  Where  more  than  one  type  of  trouble  exists,  all  will  be  repeated 
every 90 seconds.   
Battery Installation and Replacement: 
Warning:  Always  install  a  new  battery of  one  of  the  approved  types  as  listed  in  the 
Specifications  section  of  this  manual  and  the  product  label
.  When  a  battery  is  first 
inserted, a low battery test is performed. If the battery passes the test, The unit should not 
send a low battery signal. If the battery does not pass this test, the unit will continue to send 
a low battery until a good battery is installed.