☞ No problem with accessing by card, but cannot access with the PIN input. 
Cause  An error in Setup or possible component defect. 
Solution  1. Check whether a beep sound is generated when you press a key. 
When a beep sound is generated, the problem may be an error in setup. Proceed like followings: 
- Enter the Master ID (“00000000” default) to enter the Setup mode. 
- Press <F2> key.   
- [LANGUAGE] will appear on the LCD, then use the key <6> to choose [RD1_PIN_INPUT] and 
select ‘USE’ as wanted. 
2. When there is no beep sound or already enabled Key-in functions, contact a designated service center. 
 
☞ The Setup mode suddenly goes back to the Normal operating mode. 
Cause  Time out error 
Solution    In the Setup mode, it is programmed to do so when there is no key-in or reading card within 60 seconds. 
 
 
 
 Keeps making buzzer sound: “beep~ beep ~ beep” or “beeeeeeeep~~~~”. 
Cause  Error in Installation, Door status or Internal circuits. 
Solution  1. Check the door status. It occurs in case that the door is opened over 3sec(Default) after the proper door 
open time.   
2. Check the door contact sensor type: it should be NO type. 
3. Check in [7. OUTPUT T/S] of F6, the ten Time schedule code (01~10) value of output T/S. If the time 
schedule code is set between 01 up to 10 and if the present time is included in the schedule.   
If it is set to unintended value, change it to “00” ( Programmable via PC software) 
4. Check in Tamper switch of GE313.     
5. If the trouble remains after checking the above, contact a designated service center.