Справочник Пользователя для RadioFrame Networks Inc MCSERIESHP10
System Definition
MC-Series High-Power System
998--01
Rev
X1
34
CONFIDENTIAL AND PROPRIETARY
RadioFrame Networks, Inc.
TRADE SECRET INFORMATION
2.5.5 Power Consumption
Table 11 Power Consumption per Assembly (See Note)
Assembly
Qty
Power per
Assembly (W)
Total Power
(W)
Current
(A
@
–48 VDC)
RF Shelf
3 532.7
1305.6 29.2
RBS (24 RadioBlade
transceivers)
transceivers)
1 67.2
67.2 1.4
BIC
1 110.0
110.0 2.3
AIC
1 115.2
115.2 2.4
ISC
2 24.0
48.0 1.0
EAS
1 19.2
19.2 0.4
CSU
1 40.0
40.0 0.8
TOTAL 1705
35.5
Note: Panduit termination lugs are required for installation. Wire size is AWG 6.
2.5.6 Grounding
Table 12 Grounding Resistance at Cabinet (TOR)(See Note)
Supplier
Component
Ground Resistance (Ω)
RadioFrame Networks
cabinet
0.6
Note: Panduit termination lugs are required for installation. Wire size is AWG 6.
2.5.7 Heat Load
Table 13 Heat Load
Supplier
Component
Heat Load (BTUs per Hour)
BIC 340
AIC 340
RBS 320
RF Shelf
TBD
RadioFrame Networks
PDU 10
iSC-3 140
EAS 170
Non-RFN
CSU 140
TOTAL
2.5.8 RF Performance
The MC-Series system will meet the emissions mask requirements per FCC Part 90,
section 90.691.
section 90.691.