PRELIMINARY: Notifier Wireless Sensor Network — P/N LS10036-000NF-E:N0 10/10/2013
Devices
Device Operations
Panel Indication Devices that are in the tampered condition reports a latching trouble event.
The event is active for 180 seconds before it can be removed with a system reset. Once the event is
removed, the device reports a "NO ANSWER' or "INVALID REPLY" until the device is restored or
the point is removed from the database.
Clearing the Tamper To clear the tamper,
Clearing the Tamper To clear the tamper,
• If it is a detector, ensure that the detector is locked together with its base.
• If it is a module, ensure that there is a magnet in the cover plate, and is securely fastened to
• If it is a module, ensure that there is a magnet in the cover plate, and is securely fastened to
the device in the right orientation.
Once the tamper event is cleared, the LEDs in the device emit solid light for 2.5 seconds, in the fol-
lowing color patterns that denote the battery status.
• Green - All the four batteries are installed and fresh. The device has a minimum one year of
normal operation.
• Yellow - All the four batteries are installed, and one or more is no longer fresh. This device
has- between a minimum of 1 month and 1 year of operation.
• Red - One or more of the batteries are low in power and the device has less than a month of
operation.
After the device displays the current battery condition, it attempts to join the mesh network in the
rescue mode or normal mode. This is indicated by a double yellow blink every 3.4 seconds. If a
device does not find its mesh in the rescue mode, it searches for its mesh under formation. This is
indicated by a double yellow blink every 20 seconds.
Duplicate Address
Two wireless devices on the same mesh network that are set to the same address reports a duplicate
address trouble. The device(s) blink the address fault condition of a single yellow blink every 3.4
seconds. The FWSG will respond to the panel with the device type of the first device to join.
The panel displays “DUAL ADDR” or “DUALAD” during a duplicate address condition.
The panel displays “DUAL ADDR” or “DUALAD” during a duplicate address condition.
No Answer
A device that is not in the mesh, displays a “NO ANSWER” or “INVREP” message at the FACP.
Follow the steps in topic, “Mesh Formation Mode” to get a device in the mesh.
Jamming
Jamming occurs when a device is overloaded with an interfering RF signal; but is able to send the
messages out. A jamming event is detected after 20 seconds of exposure to the jamming signal. In
the event of jamming, the LED emits a single yellow blink every 13.6 seconds. Prolonged dura-
tions of jamming results in the jammed device dropping from the mesh network. The panel dis-
plays “RADIO JAMMING” or “JAM” during a jamming condition.
Device Initialization
A device reports a device initialization trouble when it is part of a mesh network but is not capable
of performing fire protection. This is the case for mesh networks that are still forming and optimiz-
ing.
The panel displays “INIT MODE” or “INIT” during a device initialization condition.
The panel displays “INIT MODE” or “INIT” during a device initialization condition.