TM70Pi V3.2 (11/03) 120021.pdf.
58
IKUSI reserves the right to change this information without prior notice.
TM70 – ANALOGUE FEEDBACK CALIBRATION
14.1 - INTRODUCTION
Systems with analogue feedback need to have the options Display and Analogue Feedback.
Systems with analogue feedback need at startup the calibration of the analogue input by the
distributor or the user. The following steps need to be done:
14.2 - CALIBRATION OF THE ANALOGUE FEEDBACK WITH LCD DISPLAY
Transmitters with display option, allow the operator the calibration of the analogue input through the
edition of a three digit value plus a comma and a measurement unit up to three characters.
The modified feedback calibration data will not be updated in the receiver
EEPROM. In order to do it, please copy the new information located in the
transmitter EEPROM into the receiver one.
At the remote control start up the Calibration must be done as follows:
1.
Insert a fully charged battery and turn ON the
contact key.
2.
Push and Pull the STOP pushbutton. An orange
blink will be seen on the LED followed by green
pulses and the LED switches off.
3.
Place a known load on the crane in order to
introduce the First value in Calibration mode.
4.
Switch off the remote control and start the system
entering in CALIBRATION mode. In order to do so,
it is necessary to do the following:
5.
Press LCD70 push button “ENTER” (default value)
and
press
START
pushbutton.
Keep
both
pushbuttons pushed for a couple of seconds until
the CONFIG option appears on the display.
Remark: It is possible using the TMConfig
tool to assign a different function; this
function must defined and written in the
equipment technical datasheet
6.
Press the push button “ENTER” to go into
the MENU.
7.
To  move  through  the  menu,  use  “UP”  (▲)  and  “DOWN”  (▼)  functions  the  CALIBRATION 
menu appears.
8.
Press “ENTER” function.