I210 3G SmartMeter User Guide 
 
    
 
 
 
 
13 
 
Process 
Steps 
Description 
Action 
 
Is Pin # Correct? 
Validate that the pin number in the TMS system is 
indeed the pin number that is matched with the correct 
meter.  Checking the manufacturer’s spreadsheet sent 
with the meters and/or visually inspecting the label on 
the meter can accomplish this task. 
Did site pass CVU tests? 
 
Check Meter Test Person’s site validation notes and 
verify that test were properly run and meet the minimum 
requirements. 
Get Version? 
Perform Get Version ANSI action on device. (See TMS 
User Guide) 
Restore Meter to Factory 
Defaults? 
 
Perform Restore Meter to Factory Defaults ANSI (see 
TMS User Guide) 
Get Status? 
Perform Get Status ANSI action on device. (See TMS 
User Guide) 
Get Status Successful? 
Check the results of the Get Status ANSI using Event 
Search and View Details. (See TMS User Guide) 
Execute the following Task: 
Provision 
 
Execute Provision on the meter. (See TMS User Guide) 
10 
Did the meter provision? 
 
Check the results of the Provision ANSI using Event 
Search and View Details. (See TMS User Guide) 
11 
Sync System to Device 
 
If meter is already in a Functional Group, user will need 
to execute task Sync System to device. (See TMS User 
Guide) 
12 
Put meter into production 
system 
 
Do the necessary paperwork to put meter on production 
system and notify appropriate stakeholders. 
13 
Ping the Module Using the 
Internet/Web Browser 
Go to the Network web page. Send a message tab. 
Enter in the pin number of the device and a 
miscellaneous message in the message field. Click 
Send. (See Section 4.2.1) 
14 
Is Pin Active? 
 
After using the internet/web browser, does the screen 
say message submitted (yes) or invalid pin (no)? (See 
Section 4.2.1) 
15 
Activate Pin Through Itron 
Log on to the OCS and create a new case for the invalid 
pin. Itron Personnel will take care of the issue and notify 
the user when the PIN is active.   
16 
Field Site Visit - Call into 
TMS Operator 
Dispatch a meter tech to perform the Onsite 
troubleshooting procedure and have them call into the 
TMS operator at the time of completion.  
17 
Bring Meter in for evaluation 
 
Replace meter with another SmartMeter and bring into 
Meter Shop for further evaluation.