Справочник Пользователя для Itron CENGPRS1
CENTRON GPRS SmartMeter User Guide
SMR45-4601A
15
4. SmartMeter State: provides a high-level state of SmartSynch firmware.
00
Initial state – SmartMeter not Quality Controlled yet
01
SmartMeter passed the Meter Integrator QC
02
SmartMeter passed Utility QC & is ready for deployment
03
SmartMeter is attempting to auto-configure with configuration server
04
SmartMeter is configured & is attempting to register with TMS
30
SmartMeter failed to automatically download configuration
05
SmartMeter has automatically registered with TMS
31
SmartMeter failed to automatically register with TMS
06
TMS has successfully provisioned the SmartMeter
80
SmartMeter failed to transmit messages in up to 24 hours
81
SmartMeter failed to transmit in at least 24 hours (# messages < 10)
82
SmartMeter failed to transmit in at least 24 hours (# messages >= 10)
Not ready.
Good.
Warning.
Error
States: 00 – 29; Errors: 30 – 59; Warnings: 80-99
5. Received Signal Strength Indicator (RSSI): signal strength as reported by the modem
Displayed RSSI Value
Equivalent Power Value (dBm)
0
-113 or less
1 -111
2 -109
3 -107
5 -103
7 -99
9 -95
11 -91
13 -87
15 -83
17 -79
19 -75
21 -71
23 -67
25 -63
27 -59
29 -55
31 -51
99
2 -109
3 -107
5 -103
7 -99
9 -95
11 -91
13 -87
15 -83
17 -79
19 -75
21 -71
23 -67
25 -63
27 -59
29 -55
31 -51
99
not known or not detectable