Справочник Пользователя для IBM 11000VA LCD 5U Rack UPS (200/208/230V) 53959KX

Модели
53959KX
Скачать
Страница из 20
IBM 11000VA LCD 5U Rack Uninterruptible Power Supply
6
Table 2. Specifications (continued)
Communications and management
USB port
Yes
RS-232 serial port
Yes
Ethernet port
Optional using Network Management Card, 46M4110
Environmental Monitoring Probe 
Optional Environmental Monitoring Probe, 46M4113
Surge protection and filtering  
Surge energy rating
1300 Joules
Filtering 
ANSI/IEEE C62.41; 1991 CATEGORYB3 (SURGE)
Battery run times and recharge times
Table 3 lists the expected period during which the 11000VA UPS will operate solely on batteries.
Table 3. IBM 11000VA UPS runtime chart
Load
Run time on batteries
Percent load
VA
Watts
Run time with standard internal  
battery only
Run time with internal battery plus  
External Battery Module  (EBM)
50%
5500
5000
14 minutes
35 minutes
100%
11000
10000
5 minutes
14 minutes
Note: Battery backup times are approximate and can vary with equipment, configuration, battery age, and 
temperature.
Physical specifications and operating environment
The physical specifications of the 5U uninterruptible power supply are as follows:
Height: 212 mm (8.3 in.)
z
Width: 483 mm (19 in.)
z
Depth: 740 mm (29.1 in.)
z
Weight: 99 kg (218 lb)
z
The physical specifications of the 3U Extended Battery Module are as follows:
Height: 127 mm (5.0 in)
z
Width: 483 mm (19 in.)
z
Depth: 740 mm (29.1 in.)
z
Weight: 79 kg (174 lb)
z
The IBM 11000VA LCD 5U Rack UPS is supported in the following operating environment:
Temperature: 0 - 40.0° C (32 - 104° F) at 0 - 2,000 m (0 - 6,600 ft)
z
Relative humidity: 5 - 95% 
z
Maximum altitude: 3,048 m (10,000 ft) 
z