1.5.6 Output 2 – Door status light
The open collector output 2 (I max = 100mA) is used for signaling the
status of the door (gateway occupied / free).
An external DC relay must be installed in accordance with the following
limits:
• Max relay voltage = 28VDC
• Max relay current = 100mA
• Max Vce(sat at 100mA) = 1.2V
status of the door (gateway occupied / free).
An external DC relay must be installed in accordance with the following
limits:
• Max relay voltage = 28VDC
• Max relay current = 100mA
• Max Vce(sat at 100mA) = 1.2V
It is mandatory to use the 1N4004 (or equivalent) provided diode in
parallel to the coil of the relay.
Inductive load with alternating current: not allowed
parallel to the coil of the relay.
Inductive load with alternating current: not allowed