CTK03 ComfortNet™ Communicating Thermostat
15
I/O-CHTSTAT03  69-2688—01
Setup (SETUP)
Sub-menu Item
User Modifiable Options
Comments
Heat Airflow Trim 
(HT TRM)
-10% to +10% in 2% Increments 
(Default 0%)
Trims the heating airflow by the 
selected amount.
Heat ON Delay 
(HT ON)
5, 10, 15, 20, 25, or 30 seconds 
(Default 20)
Selects the indoor blower heat on 
delay
Heat OFF Delay 
(HT OFF)
30, 60, 90, 120, 150, or 180 seconds 
(Default 120)
Selects the indoor blower heat off 
delay
Heating Air Flow 
(HT ADJ)
1, 2, 3, 4 (Default 2)
Selects the nominal heating airflow
Status (STATUS)
Sub-menu Item
Indication (for Display Only; not User Modifiable)
Mode (MODE)
Displays the current furnace operating mode
CFM (CFM)
Displays the airflow for the current operating mode
Non-Comm (Non-COMM applies only to a communicating furnace matched with a non-
communicating AC)
Sub-menu Item User Modifiable Options
Comments
Cool Airflow (CL 
CFM)
18, 24, 30, 36, 42, 48, or 
60 (Default 18)
Selects the airflow for the non-communicating 
1-stage AC unit
Cool Airflow Trim 
(CL TRM)
-10% to +10% in 2% 
Increments (Default 0%)
Selects the airflow trim amount for the 
noncommunicating 1-stage AC unit
Cool Airflow 
Profile (CL PRFL)
A, B, C, or D (Default A)
Selects the airflow profile for the 
noncommunicating 1-stage AC unit
Cool ON Delay 
(CL ON)
5, 10, 20, or 30 seconds 
(Default 5)
Selects the indoor blower on delay for the 
noncommunicating 1-stage AC unit
Cool OFF Delay 
(CL OFF)
30, 60, 90, or 120 seconds 
(Default 30)
Selects the indoor blower off delay for the 
noncommunicating 1-stage AC unit