+ ZigBee 
DIP switch 
value
RSSI trending
RSSI for a particular AZW-5000
r
Can be used to trend RSSI for a particular device.
For example, suppose you have a transceiver with a ZigBee DIP switch setting 
of 4 (device 1004), and want to setup a trendlog to monitor the RSSI value to 
that transceiver from the coordinator (device 1000). Set up a trendlog in the 
BCM monitoring AV-20004 in the coordinator. The value returned by 
AV-20004 is the RSSI value between device 1000 and device 1004.
AV-25000 
+ ZigBee 
DIP switch 
value
Reliability
Reliability data for a particular 
AZW-5000
r
Can be used to trend reliability for a particular device.
For example, suppose in a multi-hop network you have a transceiver with a 
ZigBee DIP switch setting of 6 (device 1006). It is acting as a router to a 
remote transceiver that has a DIP switch setting of 11 (device 1011). Set up a 
trendlog in the BCM monitoring AV-25011 in device 1006. The value returned 
by AV-25011 is the reliability value between device 1006 and device 1011.
BV-0
AZW-5000 
Commissioning
Commissioning changes
r/w
Indicates that commissioning data has been changed in Envision for BACtalk 
and that power needs to be cycled to write the changes to the AZW-5000. Must 
be manually set to active by the user to initiate a save of the commissioning 
data when power is cycled.
BV-1
ZigBee Status
MAC Layer Status
r
BV-2
ZigBee Status
Network Layer Status
r
BV-4
ZigBee Status
Application Layer Status
r
AZW-5000 points sorted by point number
Point
Function
Description
Default
Value
R/W
Comments