Senstar LM100 configuration overview
Senstar LM100 Product Guide
Page 47
Senstar LM100 configuration overview
To setup and calibrate the Senstar LM100:
1. Set the gateway’s Silver Network parameters, if required (see 
Silver Network Address
Silver Network configuration (Loop or Star)
IP settings for Silver Star configuration
2. Setup and define the luminaires wireless mesh network (see 
discover the devices in the mesh network
order the heads to identify locations
sequence the heads for segment and zone setup
3. Reset the Heads supervision (see 
).
4. Conduct a Sensitivity Profile for the protected fence (see 
).
5. Define the luminaires’ segment and zone settings according to the site plan (see 
).
assign the luminaires to their specific segments
assign the luminaire segments to their specific zones
6. Adjust the luminaires’ alarm detection parameters and threshold (see 
Event Window
Event Count
Alarm Window
Threshold
7. Setup the luminaires’ lighting properties and Schedule (see 
Normal Light Control
Auto Light Control
specify up to 8 independent zone-based routine lighting schedules
8. Configure the gateway’s input and output (I/O) ports (see 
define the method of I/O control
specify an I/O option card, if required
specify each of the 10 I/O ports as either an input or output
set the I/O jumpers, if required
configure the specified inputs
configure the specified outputs
9. Test the installation (see 
).
Senstar LM100 definitions
head - Head is the term used to describe the electronic components of the luminaire. Each 
luminaire includes a head. The UCM uses the head to define segments, which are in turn 
assigned to zones. Each head is identified by a 5-digit mesh network Id (the head network Id is 
not related to the gateway’s Silver Network address).