The Threshold is usually set with respect to the recorded Sensitivity Profile. Select a segment,
then use the Threshold: spin controls to set the Threshold for that segment. A good starting point
is to set the Threshold just below the recorded Sensitivity Profile in each segment. You can use the
up down arrows beside the segment setting window to lower, or raise the Threshold for all defined
segments.
then use the Threshold: spin controls to set the Threshold for that segment. A good starting point
is to set the Threshold just below the recorded Sensitivity Profile in each segment. You can use the
up down arrows beside the segment setting window to lower, or raise the Threshold for all defined
segments.
Segment threshold setting procedure
1. Establish a UCM connection to the gateway and select the Config tab.
2. Select a segment then use the Threshold: spin controls to set the Threshold for that segment.
3. Repeat for each defined segment.
4. Use the Threshold adjustment arrows to adjust the Threshold for all installed luminaires, if
2. Select a segment then use the Threshold: spin controls to set the Threshold for that segment.
3. Repeat for each defined segment.
4. Use the Threshold adjustment arrows to adjust the Threshold for all installed luminaires, if
desired.
5. Save the UCM file and download the configuration data to the gateway.
illustrates a Segment setting window for an LM100 system, which has been split into 6
segments and 5 zones. Segments 1, 2, 4 and 5 (Zones 1, 2 and 4) use the same Threshold
setting. Segment 4 (Zone 3) is considered a high threat area and the Threshold has been set to a
lower value to increase the detection sensitivity in that zone. Segment 3 represents a group of
luminaires that are used exclusively for lighting purposes (no alarm detection required) so the
segment Threshold is set to the maximum value of 255.
setting. Segment 4 (Zone 3) is considered a high threat area and the Threshold has been set to a
lower value to increase the detection sensitivity in that zone. Segment 3 represents a group of
luminaires that are used exclusively for lighting purposes (no alarm detection required) so the
segment Threshold is set to the maximum value of 255.
Note
Left-clicking in the Segment window and using the up and down arrows
on the keyboard, or the mouse wheel will also adjust the Threshold.
on the keyboard, or the mouse wheel will also adjust the Threshold.
Note
Set the Threshold after the Sensitivity Profile is completed and
downloaded to the gateway.
downloaded to the gateway.
Note
Intrusion testing is used to verify the Threshold settings.
Figure 54: Setting the segment Thresholds
Threshold
lower Threshold setting
for high security Zone 3
Threshold set for scheduled light
control without alarm detection
(segment Threshold set to 255)