LC 1200 Manual                                                                                                    The LC 1200 System 1-3                          
Double conditioning – Door with Lock(s) 
Notes: Although most locks can be interfaced 
with an LC unit, the instructions hereafter are 
only applicable to an Accutech supplied 3101 
Magnetic Lock.  
If an active Tag enters a monitored door zone, 
the system will detect the Tag. At that moment 
(provided the door is closed, has a Magnetic 
Lock(s), and the Lock is unobstructed) the 
Magnetic Lock will energize, locking the door. 
The Lock will remain locked for as long as the 
Tag is in the monitored zone. When the Tag 
leaves the monitored zone, the door will unlock 
after an adjustable period of time (02-18 
seconds; set by potentiometer R43 (Tag Detect 
Delay).  
Accutech’s 3101 Magnetic Locks also 
incorporates Delayed Egress Circuitry that 
complies with N.F.P.A. 101 Life Safety Codes 
5-2.1.6.1. If engaged, the Lock will release 
within 15 seconds (after 1-3 second nuisance 
delay) whenever a maintained force (less than 15 
pounds required) is applied to the door. An 
audible tone enunciates both countdown and 
release. When the Lock releases, the red LED 
will turn solid green and the Lock alarm will 
sound continuously. However, if the door is not 
opened and the Tag leaves the zone, the audible 
tone will cease and the Lock will return to 
normal operation. 
The Lock will NOT engage (or will disengage) 
when the facility’s Fire Alarm is activated or 
power is lost.   
 
 
Double conditioning - Elevator 
Note: The use of Elevator Deactivation with the 
LC unit will require a relay board. 
Elevator Deactivation Circuitry restricts the 
wearer of a Tag from using an elevator. If a Tag 
enters a monitored elevator zone, the elevator’s 
call button on that floor will be deactivated (Call 
buttons on other floors are unaffected and no 
one is restricted from coming to the floor). 
If the elevator car is en route to the floor when a 
Tag approaches the zone, the elevator will arrive 
on the floor, the door(s) will open, and the 
system will alarm. 
When a Tag is in the zone (or approaches the 
zone) and the elevator doors are open, the doors 
will remain open and an alarm will sound. 
Double Conditioning - Automatic Door 
If an active Tag enters a monitored automatic 
door zone, the system will detect the Tag and the 
automatic door operation (motion detector 
and/or push paddle) will be disabled.  If the door 
is manually opened while the Tag is in the zone, 
an egress alarm will be generated. When the Tag 
leaves the zone, the door will return to normal 
operation after an adjustable period of time (02-
18 seconds; set by potentiometer R43 (Tag 
Detect Delay).  
To clear this alarm, remove the Tag from the 
zone, close the door, and enter a valid code into 
the zone Keypad.