Справочник Пользователя для Lutron Electronics Company Inc 0083
Lutron Electronics Co., Inc.
Made and print ed in the U.S.A.
P/N 030-1603 Rev. A 07/2011
Made and print ed in the U.S.A.
P/N 030-1603 Rev. A 07/2011
Technical support: USA, Canada, Caribbean: 1.800.523.9466
Mexico: +1.888.235.2910
Central/South America: +1.610.282.6701
Warranty: 1-year limited warranty standard. 2-year parts and labor warranty, with
8-year pro-rated parts replacement on systems that include factory startup.
Lutron and the sunburst logo are registered trademarks and FASS and Stanza are trademarks
of Lutron Electronics Co., Inc.
© 2011 Lutron Electronics Co., Inc.
of Lutron Electronics Co., Inc.
© 2011 Lutron Electronics Co., Inc.
®
Dimming Slider
Slide up to brighten; slide down to dim
Load must be on for slider to affect intensity
Switch operation (SZ-6ANS)
Indicator light in slider track
Glows softly green for easy locating of control
Track ends flash amber to indicate programming/
addressing mode
Tapswitch
Turns load on to slider level and off
FASS
TM
Front-accessible service switch (facilitates safe bulb
replacement)
Pull down to remove all electrical power from load
and deactivate dimmer
Push up to restore power to load and dimmer
Indicator light
Glows softly green for easy locating of control
Ends flash amber to indicate programming/
addressing mode
Tapswitch
Turns load on and off
FASS
TM
Front-accessible service switch (facilitates safe bulb
replacement)
Pull down to remove all electrical power from load
and deactivate switch
Push up to restore power to load and switch
Lamp Replacement
WARNING - Shock hazard - Working with power ON may result in serious
injury or death. For any procedure other than routine lamp replacement,
disconnect power at the main electrical panel.
injury or death. For any procedure other than routine lamp replacement,
disconnect power at the main electrical panel.
For routine lamp replacement, remove power from the fixture(s) by pulling down
the FASS switch on the Dimmer / Switch.
Troubleshooting Guide
Symptom
Cause and Action
Load is off and there
is no indicator on the
dimmer/switch
Power not present
• Circuit breaker OFF or tripped. Perform short circuit check.
• FASS is in the OFF position. Move FASS to the ON position by
• Circuit breaker OFF or tripped. Perform short circuit check.
• FASS is in the OFF position. Move FASS to the ON position by
fully pushing it up.
Wiring error
• Check wiring to be sure it matches installation instructions
• Check wiring to be sure it matches installation instructions
and wiring diagrams.
Lamps burned out or not installed (SZ-6D only)
• Replace or install lamps.
• Replace or install lamps.
Dioded lamps
• Replace with non-dioded lamps.
• Replace with non-dioded lamps.
Damaged dimmer/switch
• Device may have been damaged by previous overload or
• Device may have been damaged by previous overload or
miswire. Replace device.
Dimmer / switch indica-
tor is on but load can-
not be turned on and/or
cannot be turned off
Wiring error
• Check wiring to be sure it agrees with installation instructions
• Check wiring to be sure it agrees with installation instructions
and wiring diagrams.
Lamps burned out or not installed (SZ-6ND, SZ-6ANS)
• Replace or install lamps.
• Replace or install lamps.
Damaged dimmer/switch
• Device may have been damaged by previous overload or
• Device may have been damaged by previous overload or
miswire. Replace device.
Light turns ON and OFF
continuously
Load is less than minimum load requirement
• Make sure the connected load meets the minimum load
• Make sure the connected load meets the minimum load
requirement for that control. See Load Specifications table.
Improper load type
• Check that the load being dimmed is dimmable. See Load
• Check that the load being dimmed is dimmable. See Load
Specifications table.
Lights don’t switch ON/
OFF from keypad
Improper programming
• Check programming in the Stanza software.
Out of RF range
• Ensure device is within 30 feet (9 m) of another device
• Check programming in the Stanza software.
Out of RF range
• Ensure device is within 30 feet (9 m) of another device
configured as a repeater.
Wiring
• Wiring error. Check wiring to be sure it agrees with installa-
• Wiring error. Check wiring to be sure it agrees with installa-
tion instructions and wiring diagrams.
Faceplate is warm
Solid-state control dissipation
• Solid-state dimmers and switches internally dissipate about
• Solid-state dimmers and switches internally dissipate about
2% of the total connected load. It is normal for dimmers and
switches to feel warm to the touch during operation.
Control is buzzing or
humming
It is normal for dimmers and switches to emit a slight buzzing or
humming sound.
Single Location Installation
SZ-6D
SZ-6D
Wiring Diagram 1
Dimmer
Brass
Black
Lighting
load
Hot/Live
Neutral
Green
Ground
120 V
~
50 / 60 Hz
Single Location Installation with Neutral
SZ-6ND, SZ-5NE, SZ-6ANS
SZ-6ND, SZ-5NE, SZ-6ANS
Dimmer/Switch
Brass
Black
Load
Hot/Live
Neutral
Green
Ground
120 V
~
50 / 60 Hz
Silver
Dimmer operation (SZ-6D, SZ-6ND, SZ-5NE)
Wiring Diagram 2