USING THE FILLER PIECE AS A REQUEST TO EXIT SWITCH
INSTALLATION REQUIREMENTS FOR UL
294 COMPLIANCE
The EntryProx Model 4045AGU00 complies with the UL294
Standard for access control units in a standard, wall-mount
installation, when installed to the following specifications:
Standard for access control units in a standard, wall-mount
installation, when installed to the following specifications:
• Electric locking mechanisms may only be connected to
the NO contacts of the Main Relay. Locking devices
requiring an NC connection may only be used in
conjunction with an interposing relay mounted inside the
secure area and connected to the NO contacts of the
Main Relay.
requiring an NC connection may only be used in
conjunction with an interposing relay mounted inside the
secure area and connected to the NO contacts of the
Main Relay.
• The recommended or equivalent shielded wiring must be
used for the following applications: