S e c t i o n   5 :   C h a n g i n g   O t h e r   N T 9 0 1 0  
F u n c t i o n s
Most installations will only require basic programming. You can complete the basic programming using the NT9010 Installation Wizard 
(please see the NT9010 Quick Set Up Guide for more information). This section explains programmable features that affect the internal 
functioning of the system, including zone operation, central station communications, talk/listen-in features, computer downloading fea-
tures, and other advanced options.
5.1
Zone Definitions
You can change how each of the 32 zones will operate in pro-
gramming sections [001] - [004]. For each zone that will be used, 
enter a 2-digit zone definition.
NOTE:
In addition to selecting how each zone will operate, 
attributes may be programmed by zone (section 5.2 “Zone 
Attributes”
 on page 16).
[00]
Null Zone: The zone will not operate in any way. Zones 
that are not used should be programmed as Null zones.
[01]
Delay 1 Zone: If this zone is violated when the system is 
armed it will provide an entry delay. The keypad buzzer 
will sound to warn the user that the system must be dis-
armed. If the system is not disarmed before the entry 
delay expires an alarm will be generated. Typically this 
type of zone will be used for the front door, back door or 
any other entry/exit point. Refer to Section [005], “System 
Times”, to program the Delay 1 zone entry delay time.
[02]
Delay 2 Zone: This zone type operates the same as the 
Delay 1 zone option but can provide a different entry 
delay. Typically this zone will be used for a garage door. 
Refer to Section [005], “System Times”, to program the 
Delay 2 zone entry delay.
[03]
Instant Zone: If this zone type is violated when the sys-
tem is armed it will cause an instant alarm. Typically this 
zone is used for windows, patio doors or other perimeter 
type zones.
[04]
Interior Zone: If this type of zone is violated when the 
system is armed it will provide entry if a delay type zone 
was violated first. Otherwise it will cause an instant alarm. 
Typically this zone is used for interior protection devices, 
such as motion detectors.
[05]
Interior Stay/Away Zone: This zone type works the 
same as the Interior zone type with one exception. The 
zone will be automatically bypassed under the following 
conditions:
•  the system is armed in the Stay Mode (section 4.10 
“Function Keys”
 on page 12)
•  the system is armed without entry delay (section  “[*] 
[9] Arming Without Entry Delay”
 on page 12)
•  the system is armed with an access code and during 
the exit delay a Delay type zone is NOT tripped
The automatic bypass avoids having the user manually 
bypass interior type zones when arming at home. If auto-
matically bypassed, the user can reactivate the zones by 
entering the [*][1] command (section  “[*][1] Zone 
Bypassing”
 on page 10). Typically this zone is used for 
interior protection devices, such as motion detectors.
[06]
Delay Stay/Away Zone: This zone type will operate the 
same as the Interior Stay/Away zone type except that it 
will always provide entry delay. Typically this zone is used 
for interior protection devices, such as motion detectors 
and will help prevent false alarms since it will always pro-
vide the user the entry delay time to turn off the system.
[07] - [09] For future use
[10]
24 Hour Supervisory Buzzer Zone:   Whether armed or 
disarmed, when this zone type is violated the system will 
immediately latch the keypad buzzer until a valid access 
code is entered and will communicate immediately to the 
central station.
[11]
24 Hour Burglary Zone:   If this zone is violated, 
whether armed or disarmed, the system will immediately 
latch the alarm output and communicate to the central 
station. The alarm will sound for the Bell Cutoff time pro-
grammed in Section [005] “System Times” or until a valid 
access code is entered.
[12]-[20]:
The following zone definitions operate similar to the 24 
Hour Burglary except for System Event output type, SIA 
identifier, and some zone attributes:
[12]
24 Hour Holdup Zone
[13]
24 Hour Gas Zone
[14]
24 Hour Heat Zone
[15]
24 Hour Medical Zone
[16]
24 Hour Panic Zone
[17]
24 Hour Emergency Zone
[18]
24 Hour Sprinkler Zone
[19]
24 Hour Water Flow Zone
[20]
24 Hour Freezer Zone
NOTE:
 [12] 24 Hour Holdup zones give a silent alarm by 
default.
[21]
24 Hour Latching Tamper:   If this zone is violated the 
installer must enter Installer Programming before the sys-
tem can be armed. The bell output will also activate for 
the programmed time and the system will communicate 
the alarm.
[22]
Momentary Keyswitch Arm Zone:   Momentary viola-
tion of this zone will alternately arm/disarm the system.
[23]
Maintained Keyswitch Arm Zone:   When this zone is 
violated, the system will arm. When this zone is secured, 
the system will disarm.
NOTE:
Do not program wireless zones as [21] or [22] Key-
switch zones.
[24]
For future use
[25] Interior 
Delay 
Zone: 
When the system is fully armed (i.e. 
away armed), this zone will follow the exit delay. It will 
also follow the entry delay, provided that a delay zone is 
tripped first. If the delay zone is not tripped first, a zone