If the PC5132 module does not show on the keypad, one of the following
conditions may be present:
• the module is not connected properly to the Keybus
• there is a problem with the Keybus wiring run
• the module does not have enough power
• no devices have been enrolled on the PC5132
4.3 Enable Supervision of Wireless Zones
NOTE: (for PC5010 v1.x control panels only) In order for wireless zones to be
supervised, you must enable Double End of Line (DEOL) supervision in the
PC5010 control panel. For more information, refer to your Installation Manual.
NOTE: (PC501X, PC1555, PC580  v2.0 and higher only) For wireless supervi-
sion to work, you must enable the wireless zone attribute on all wireless zones
(sections [101] to [132], option [8] ON).
Wireless Supervisory Window
Each wireless zone (WLS906-433,WLS904-433 or WLS925-433) will send a
supervisory signal every 64 minutes. If the receiver does not receive a signal
within the time programmed for the 
Wireless Supervisory Window
, it will
generate a supervisory fault.
To program the wireless supervisory window:
1. Enter [✱][8][Installer Code] to enter Installer Programming.
2. Enter [804] to enter the PC5132 Module Programming.
3. Enter section [81].
4. Enter the time period for the supervisory window. The window is
programmed in 15 minute increments. The default programming is 96
(x15minutes), which is equal to 24 hours. Valid entries are (08) - (96),
equal to 4 - 24 hours.
5. To exit press [#].
Disable/Enable Zone Supervision
All wireless zones have supervision enabled by default. To disable supervision
for any zone, enter the following at any system keypad:
1. Enter [✱][8][Installer Code] to enter Installer Programming.
2. Enter [804] to enter the PC5132 Module Programming.
3. Enter sections [82], [83], [84] and [85]. Enable or disable supervision for
each wireless zone by turning each relevant option on or off.
4. To exit press [#].