7.1 LE4010 IM Wiring Diagrams
The following wiring diagrams are examples of ULC Listed Fire Monitoring Installation connections.
Figure 10-4 Wiring Diagram for Fire Alarm Control Unit (with dialler) and Cellular Transmitter (Passive Com-
munication System)
 
 
 
 
 
 
 
 
 
 
 
         
  AUX Power 
(12V/700mA) 
RM1C ULC 
Relay 
Fire Alarm 
Control Unit 
TIP/RING 
Zone Input        
          
Outputs 
Fire
Trouble  
3G Cellular
Transmitter 
 
3G4010
T1/R1 
                
TIP/RING
Zone 
     
PGM4
Inputs        Output  
3G4010 cabinet 
3G (HSPA) or
2G (GPRS)
AC Input 
PSTN
Notes:
l
Power for the 3G4010/LE4010 shall be provided from the Fire Alarm Control Unit or separately listed
power supply rated for the application (12V/700mA).
l
All wiring connections must be run in a protective conduit.
l
For local supervision of the wireless transmitter, connect PGM output from 3G4010/LE4010 to one
zone input on the Fire Alarm Control Unit.
l
Dry Contact Trouble output from ULC Listed Fire Alarm Control Unit must be connected to zone input
on the 3G4010/LE4010 for supervison of Tip/Ring connection.
l
Fire Alarms must be sent over both communication channels. Fire output from Fire Alarm Control Unit
must be connected to input 1 on the 3G4010/LE4010.
l
24 hour Test Transmission must be enabled on the dialler and on the 3G4010/LE4010.
Figure 10-5 DSC Subscribers’ Unit Fire and Cellular Transmitter Mounted in the Same Room
 
 
DSC
Subscribers’ 
Unit Fire
Zone
Inputs
        TIP   
TIP            RING 
                 PGM1  
DSC Keypad 
LCD4501 
PK55XX
3G Cellular
Transmitter 
3G4010
T1/R1     
           TIP/RING 
Zone         
Input         PGM4 
AUX Power 
12V/700mA 
RM1C ULC 
Relay 
PC5003C
PC4050CR
cabinet
3G (HSPA)/2G (GPRS)   
PSTN
AC Input 
AC Input 
PC4020 
PC1864 
PC1832 
PC1616
RM1C ULC 
Relay 
3G4010 cabinet 
Outputs
Fire
Supervisory
 Trouble
Fire Alarm Control Unit
Notes:
l
Power for 3G4010/LE4010 must be provided from Fire Alarm Control Unit or separately listed power
supply rated for the application (12V/700mA).
l
All wiring connections must be run in a protective conduit.
l
Phone Line Monitoring (TLM) must be enabled.
l
Phone Line trouble is indicated by the Blue LED on the 3G4010/LE4010.