IR5 (Infrared) 
Table 2 e528 IR5 Characteristics 
Performance 
IR5 
Indoor Range 
Up to 80ft 
IR Data Rate 
2500 bps 
The  IR  Eye5  works  within  INNCOM's  System-5  protocol  and  can  be  used  in  a  fluorescent  light  environment. 
However, it may be subject to interference from plasma televisions, and care must be taken in situating the device 
if a plasma television is present. 
Installation Requirements 
Location: The e528 must be located on a partitioning interior wall, approximately 1.5 m (5 ft) above the floor, in a 
site of average temperature. It is important to ensure that the thermostat is located away from direct sunlight or 
radiant heat, air discharge grills, stairwells, outside doors, steam or water pipes, warm air stacks, 
unheated/uncooled areas, or sources of electrical or radio interference. The unit should not be placed on an outside 
wall or behind a door. It is essential that the e4 is mounted flush to the wall and mounted level in both the horizontal 
and vertical planes; incorrect mounting can degrade IR, PIR, and temperature measurement performance. 
Installation Requirements for e4 equipped with PIR Motion Detection 
The e4 thermostat can be equipped with a PIR detector to augment the energy management scheme by detecting 
motion in the guestroom. Consider the PIR’s view angle, range characteristics, and mounting position to ensure 
proper coverage. Figure 3 below shows the ranges of the flat and standard PIRs. 
 
 
 
Flat PIR Detection Range (Single Pyro) 
Standard PIR Detection Range (Dual Pyro)
 