DC Power
The TB8100 12 V PA is designed to accept a nominal 12 VDC input with 
negative ground.  There is a minimum DC start-up threshold to prevent 
damaging a battery which has little capacity left.
You must connect the DC supply from the battery to the PA via a fuse or 
DC-rated circuit breaker with the appropriate rating, as shown in the table 
below.  The DC input leads should be of a suitable gauge to ensure less than 
0.2V drop at maximum load over the required length of lead.  
Figure 1.3
5W or 50W base station inputs and outputs - rear view
b
system interface connector
f
RF output
c
external reference frequency input
g
RF input
d
12VDC input
h
auxiliary DC input for system interface
e
Power Saving control input
i
subrack ground connector
c
d
e
f
g
h
PA
reciter
b
i
Nominal Supply 
Voltage
Input Voltage 
Range
Circuit Breaker/
Fuse Rating
Recommended 
Wire Gauge
a
a. For a length of 1.5m to 2m (5ft to 6.5ft) (typical).
12VDC
10.6VDC to 16.8VDC 20A
2AWG / 35mm
2