XTLplus Installation and Programming Guide 
Digital Monitoring Products
43
APPENDIX
 
Trip Counter For DMP Wireless Check-in Test (WLS)
Displays the number of wireless zones that automatically communicate a 
supervisory check-in message.
• The number of zones that check in. (XXX in the example).
• The total number of wireless zones programmed for supervision that should 
check in. (ZZ in the example).
END - Select END to stop the Wireless Check-in Test. When the test ends or 
a 20-minute time-out expires, normal wireless zone processing returns. If all 
transmitters check-in, both numbers will match within three (3) minutes. If a 
transmitter has multiple zones (1101, 1114, etc.), all zones will be included in the 
counts. Failed wireless zones then display on the keypad.
 
Test End Warning
When no zones have been tripped and five minutes remain on the 20 minute Walk Test 
timer, the keypad displays 
TEST END WARNING and the keypad tones. If no additional 
test zone trips occur, the test ends and a final Sensor Reset automatically occurs. The 
System Test End message is sent to the receiver along with Verify and Fail messages 
for each zone under WALK test. Faulted zones then display on the keypad.
 
Failed Zones Display
Each zone that did not trip at least once during the Walk Test displays on the keypad 
that initiated the test. Any Fire (FI) Panic (PN) or Supervisory (SV) 24-hour zone 
that is faulted at the end of the Walk Test displays a trouble condition for that zone 
regardless of the message programmed for the open or short condition of the zone 
and a zone trouble is sent to the receiver. Press the COMMAND key to display the next 
failed zone.
For the Wireless Check-in Test, failed wireless zones display only on the keypad. 
Zone Verify/Fail reports are not sent to the central station receiver for the 
wireless checkin test.
36.6  Keypad Speaker Operation
When using LCD Keypads, the panel provides distinct speaker tones from the keypad for Fire, Burglary, Zone 
Monitor, and Prewarn events. The list below details the conditions under which the speaker is turned on and 
off for each event.
Fire   
On - Fire zone alarm and Bell Output are ON. 
 
 
Off - Alarm Silence or briefly when a key is pressed.
Burglary 
On - Burglary zone alarm and Bell Output and is ON. 
  
Off - Alarm Silence or briefly when a key is pressed.
Zone Monitor On - One time only when a monitored zone is tripped. 
  
Off - After one tone.
Prewarn 
On - During Entry Delay. 
  
Off - When Entry Delay expires, when a Valid Code is entered, or when a key is pressed.
36.7  Cross Zoning
Caution must be taken when cross zoning devices to ensure that the Cross Zone Time is long enough to allow 
an intruder to trip both devices before it expires. A Cross Zone Time that is too short may allow an intruder 
to trip the devices and allow only a zone fault report be sent to the central station.
When a Cross Zoned zone trips, a FAULT report is sent to the SCS-1R Receiver. When two Cross Zoned zones 
trip within the Cross Zone Time, both zones send ALARM signals to the receiver. For example, if zones 1 and 
2 are Cross Zoned zones, and only zone 1 trips, a FAULT report is sent to the receiver for zone 1. If zone 1 
trips and zone 2 trips within the Cross Zone Time, an ALARM report is sent to the receiver for zone 1 and 
zone 2.
Note: To operate correctly, all cross-zone zones need to be programmed as the same zone type.
WALK TEST
TRIPS: XXX  
END
TEST END WARNING
SOUTH LOBBY
ZONE: 10
-FAIL