Справочник Пользователя для Honeywell International Inc. 8DL5800CO

Скачать
Страница из 4
– 2 –
 
BATTERY INSTALLATION AND REPLACEMENT 
To replace the battery: 
1. 
Remove the detector from its mounting base by twisting the 
detector counterclockwise. Remove the battery, and dispose 
properly. 
2. 
To ensure proper power-down sequence, wait a minimum of 20 
seconds before installing new battery. 
3. 
Install a new 3-volt CR123A Lithium battery in the battery 
compartment. Follow the polarity diagram inside the 
compartment. 
4. 
Reinstall the detector onto the mounting base by turning the 
detector clockwise. 
5. 
Test the detector as described in the TESTING SIGNAL 
STRENGTH section of this manual. The green LED should 
blink about once every 10 seconds to indicate normal operation. 
If the battery is not installed correctly, the detector will not 
operate and the battery may be damaged. If the detector does 
not appear to be sending a signal during any of the tests, check 
for correct battery installation and for a fully charged battery. 
DO NOT
PA
IN
T
TEST BUTTON
GREEN LED
RED LED
5800CO-001-V0
 
Figure 1. 5800CO Wireless Carbon Monoxide Detector 
PROGRAMMING 
The detector must be enrolled in the control panel before it can 
operate in the system. The detector’s protection zone must be 
enrolled as Loop 1 and “Input Type” 3 (supervised RF). 
A tamper condition is transmitted as Loop 4, but does not require 
programming.   
1. 
Enter the control’s Zone Programming mode. 
2. 
Enter the zone number to be programmed. 
3. 
Enter the applicable zone type when prompted. For 
Honeywell residential controls, program loop 1 as carbon 
monoxide zone type 14). 
4. 
When prompted, enter Input Type 03 (3 on some controls) 
– Supervised RF Transmitter. 
5. 
When prompted for the serial number, transmit from the 
detector by activating the tamper switch. To do this, hold 
the base of the detector in one hand, and rotate the 
detector counter-clockwise on the base until it snaps open. 
 
Then return to clockwise position until the detector snaps 
into place.  
6. 
When the serial number is displayed, transmit from the 
detector a second time by activating the tamper switch 
again as described in Step 5.  The current loop number (4) 
will begin to flash. 
7. 
Manually change the loop number to the desired loop 
number for the zone (according to the application). 
WARNING:  The carbon monoxide protection zone enrolled 
must always be Loop 1.  Otherwise, annunciations will not be 
reported by the control. 
8. 
Exit Programming mode when programming is complete, 
and test the detector. Refer to the Testing Section. 
See the control unit’s installation instructions for further 
details.  
 
MOUNTING THE DETECTOR 
First, determine the best location for the detector, one that provides 
proper gas detection (see Figure 4 for suggested detection locations) 
and a strong wireless transmission path.  
Proper Gas Detection Location 
In a wall location, the detector should be at least as high as a light 
switch, and at least six inches from the ceiling. In a ceiling location, 
the detector should be at least 12 inches from any wall. 
 
Where to install, ideally: 
•  Within 10 feet of all sleeping areas 
•  Inside the bedroom if it contains a fuel burning appliance 
•  On every floor of the building 
•  Ideally, install in any room that contains a fuel burning 
appliance 
•  If the appliance in the room is not normally used, such as the 
boiler room, the detector should be placed just outside the room 
so the alarm can be heard more easily 
 
Where NOT to install, ideally: 
•  Detectors operate best if not installed within 10 feet of any 
cooking appliance 
•  Directly above a sink, cooker, stove or oven 
•  Next to a door or window that would be affected by drafts i.e. 
extractor fan or air vent 
•  Outside 
•  Do not install in any environment that does not comply with the 
detector’s environmental specifications 
•  In or below a cupboard 
•  Where air flow would be obstructed by curtains or furniture 
•  Where dirt or dust could collect and block the sensor 
•  Where it could be knocked, damaged, or inadvertently removed 
 
Good Transmission Path 
A GOOD TRANSMISSION PATH MUST BE ESTABLISHED 
FROM THE PROPOSED MOUNTING LOCATION BEFORE 
PERMANENTLY INSTALLING THE DETECTOR. To check, 
perform the test described in the TESTING SIGNAL STRENGTH 
section. Prior to mounting the detector to the mounting base, you 
must “enroll” the detector’s serial number into the system (see the 
PROGRAMMING section).   
 
Mounting Procedure 
To mount the detector, perform the following steps: 
1. 
Once a suitable location has been determined, install the 
mounting base on the ceiling or on the wall (if local ordinances 
permit). Use the two screws and anchors provided. 
2. 
Turn the detector in a clockwise direction in the mounting base 
until it clicks into place. 
3. 
Test the detector immediately after completing the installation 
(as described in the TESTING THE DETECTOR section of 
this manual) and refer to the control system’s instructions for 
additional information concerning the use of wireless devices. 
RE
D
L
ED
F
LAN
G
E
L
O
CK
SNIP OFF FOR
T
AMPER LOCK
TAMPER RELEASE TAB
(CUT OFF SMALL TAB TO
ACTIVATE TAMPER RESIST FEATURE)
TAMPER
RELEASE TAB
DIRECT
MOUNT
HOLES
5800CO-002-V0
 
Figure 2. Detector Mounting Base