Справочник Пользователя для Honeywell International Inc. 8DL5800CO
– 2 –
BATTERY INSTALLATION AND REPLACEMENT
To replace the battery:
1.
Remove the detector from its mounting base by twisting the
detector counterclockwise. Remove the battery, and dispose
properly.
detector counterclockwise. Remove the battery, and dispose
properly.
2.
To ensure proper power-down sequence, wait a minimum of 20
seconds before installing new battery.
seconds before installing new battery.
3.
Install a new 3-volt CR123A Lithium battery in the battery
compartment. Follow the polarity diagram inside the
compartment.
compartment. Follow the polarity diagram inside the
compartment.
4.
Reinstall the detector onto the mounting base by turning the
detector clockwise.
detector clockwise.
5.
Test the detector as described in the TESTING SIGNAL
STRENGTH section of this manual. The green LED should
blink about once every 10 seconds to indicate normal operation.
If the battery is not installed correctly, the detector will not
operate and the battery may be damaged. If the detector does
not appear to be sending a signal during any of the tests, check
for correct battery installation and for a fully charged battery.
STRENGTH section of this manual. The green LED should
blink about once every 10 seconds to indicate normal operation.
If the battery is not installed correctly, the detector will not
operate and the battery may be damaged. If the detector does
not appear to be sending a signal during any of the tests, check
for correct battery installation and for a fully charged battery.
DO NOT
PA
IN
T
TEST BUTTON
GREEN LED
RED LED
5800CO-001-V0
Figure 1. 5800CO Wireless Carbon Monoxide Detector
PROGRAMMING
The detector must be enrolled in the control panel before it can
operate in the system. The detector’s protection zone must be
enrolled as Loop 1 and “Input Type” 3 (supervised RF).
operate in the system. The detector’s protection zone must be
enrolled as Loop 1 and “Input Type” 3 (supervised RF).
A tamper condition is transmitted as Loop 4, but does not require
programming.
programming.
1.
Enter the control’s Zone Programming mode.
2.
Enter the zone number to be programmed.
3.
Enter the applicable zone type when prompted. For
Honeywell residential controls, program loop 1 as carbon
monoxide zone type 14).
Honeywell residential controls, program loop 1 as carbon
monoxide zone type 14).
4.
When prompted, enter Input Type 03 (3 on some controls)
– Supervised RF Transmitter.
– Supervised RF Transmitter.
5.
When prompted for the serial number, transmit from the
detector by activating the tamper switch. To do this, hold
the base of the detector in one hand, and rotate the
detector counter-clockwise on the base until it snaps open.
detector by activating the tamper switch. To do this, hold
the base of the detector in one hand, and rotate the
detector counter-clockwise on the base until it snaps open.
Then return to clockwise position until the detector snaps
into place.
into place.
6.
When the serial number is displayed, transmit from the
detector a second time by activating the tamper switch
again as described in Step 5. The current loop number (4)
will begin to flash.
detector a second time by activating the tamper switch
again as described in Step 5. The current loop number (4)
will begin to flash.
7.
Manually change the loop number to the desired loop
number for the zone (according to the application).
number for the zone (according to the application).
WARNING: The carbon monoxide protection zone enrolled
must always be Loop 1. Otherwise, annunciations will not be
reported by the control.
must always be Loop 1. Otherwise, annunciations will not be
reported by the control.
8.
Exit Programming mode when programming is complete,
and test the detector. Refer to the Testing Section.
and test the detector. Refer to the Testing Section.
See the control unit’s installation instructions for further
details.
details.
MOUNTING THE DETECTOR
First, determine the best location for the detector, one that provides
proper gas detection (see Figure 4 for suggested detection locations)
and a strong wireless transmission path.
proper gas detection (see Figure 4 for suggested detection locations)
and a strong wireless transmission path.
Proper Gas Detection Location
In a wall location, the detector should be at least as high as a light
switch, and at least six inches from the ceiling. In a ceiling location,
the detector should be at least 12 inches from any wall.
In a wall location, the detector should be at least as high as a light
switch, and at least six inches from the ceiling. In a ceiling location,
the detector should be at least 12 inches from any wall.
Where to install, ideally:
• Within 10 feet of all sleeping areas
• Inside the bedroom if it contains a fuel burning appliance
• On every floor of the building
• Ideally, install in any room that contains a fuel burning
• Within 10 feet of all sleeping areas
• Inside the bedroom if it contains a fuel burning appliance
• On every floor of the building
• Ideally, install in any room that contains a fuel burning
appliance
• If the appliance in the room is not normally used, such as the
boiler room, the detector should be placed just outside the room
so the alarm can be heard more easily
so the alarm can be heard more easily
Where NOT to install, ideally:
• Detectors operate best if not installed within 10 feet of any
• Detectors operate best if not installed within 10 feet of any
cooking appliance
• Directly above a sink, cooker, stove or oven
• Next to a door or window that would be affected by drafts i.e.
• Next to a door or window that would be affected by drafts i.e.
extractor fan or air vent
• Outside
• Do not install in any environment that does not comply with the
• Do not install in any environment that does not comply with the
detector’s environmental specifications
• In or below a cupboard
• Where air flow would be obstructed by curtains or furniture
• Where dirt or dust could collect and block the sensor
• Where it could be knocked, damaged, or inadvertently removed
• Where air flow would be obstructed by curtains or furniture
• Where dirt or dust could collect and block the sensor
• Where it could be knocked, damaged, or inadvertently removed
Good Transmission Path
A GOOD TRANSMISSION PATH MUST BE ESTABLISHED
FROM THE PROPOSED MOUNTING LOCATION BEFORE
PERMANENTLY INSTALLING THE DETECTOR. To check,
perform the test described in the TESTING SIGNAL STRENGTH
section. Prior to mounting the detector to the mounting base, you
must “enroll” the detector’s serial number into the system (see the
PROGRAMMING section).
FROM THE PROPOSED MOUNTING LOCATION BEFORE
PERMANENTLY INSTALLING THE DETECTOR. To check,
perform the test described in the TESTING SIGNAL STRENGTH
section. Prior to mounting the detector to the mounting base, you
must “enroll” the detector’s serial number into the system (see the
PROGRAMMING section).
Mounting Procedure
To mount the detector, perform the following steps:
1.
Once a suitable location has been determined, install the
mounting base on the ceiling or on the wall (if local ordinances
permit). Use the two screws and anchors provided.
mounting base on the ceiling or on the wall (if local ordinances
permit). Use the two screws and anchors provided.
2.
Turn the detector in a clockwise direction in the mounting base
until it clicks into place.
until it clicks into place.
3.
Test the detector immediately after completing the installation
(as described in the TESTING THE DETECTOR section of
this manual) and refer to the control system’s instructions for
additional information concerning the use of wireless devices.
(as described in the TESTING THE DETECTOR section of
this manual) and refer to the control system’s instructions for
additional information concerning the use of wireless devices.
RE
D
L
ED
F
LAN
G
E
L
O
CK
SNIP OFF FOR
T
AMPER LOCK
TAMPER RELEASE TAB
(CUT OFF SMALL TAB TO
ACTIVATE TAMPER RESIST FEATURE)
TAMPER
RELEASE TAB
DIRECT
MOUNT
HOLES
5800CO-002-V0
Figure 2. Detector Mounting Base