Figure 3. Sensor Base
• When installing multiple sensors:
– DO NOT mount sensors facing each other.
– Mount them at least 20 feet (6.1m) apart.
– Mounting sensors back to back is not recommended, but
if an application requires such mounting, use the 9-foot
(2.7m) range, mount at least 1foot (0.3m) apart, and walk test
the installation to ensure proper operation.
Installing the Sensor
All wiring must conform to the National Electric Code (NEC)
and/or local codes having jurisdiction.
Important: 
DO NOT use this device for safety interlock
applications.
Use the following steps to install the sensor:
1. Run the security system wiring to the sensor location.
2. Lift off the front cover/electronic module. Remove the
nameplate and loosen the screw if necessary. See
Figure 1.
CAUTION
You must be free of all static electricity before
handling sensor circuit boards. Touch a
grounded, bare metal surface before touching
circuit boards or wear a grounding strap.
3. If necessary, set the jumpers on the circuit board. See
Setting the Jumpers
.
4. Remove the appropriate wiring and mounting knock-
outs  from the back cover. The sensor can be mounted
on a flat wall or in a corner. See Figure 3.
5. Pull the wires through the knockout holes and use the
two screws provided to attach the base to the wall. Use
screw anchors if necessary.
6. Strip 1/4 inch (6.4 mm) of insulation from each wire.
7. Run each wire through the strain relief and under the
appropriate screw terminals on the base and tighten
the screws. See Figure 3.
8. Line up the tabs on the bottom of the cover/electronic
module with the corresponding tabs on bottom of the
base and snap the cover/electronic module firmly down
onto the base.
9. Tighten the screw and replace the nameplate. See
Figure 1.
10. Apply power. The LED should light green for approxi-
mately 25 seconds and then go out.
11. Walk test the coverage pattern as follows:
– Walk throughout the intended coverage area.
– Verify the sensor alarms. See Understanding the LED.
Figure 4. Main Circuit Board
J3
J2
J2 Range
J3 LED
Disable
Terminal
sockets
Corner-
mount
knockouts
Flat wall-
mount
knockout
Flat wall-
mount
knockout
Wiring