Installation
Caution
Installation and maintenance must be performed by a qualified
electrician in accordance with local, state, and national electrical 
codes (NEC) and requirements.
LED Description
Step 1: De-energize the luminaire.
Step 2: Determine the location of the sensor. Push and 
rotate the anchor screw to the tile at that location.  
Step 3: Select a place near the anchor screw for the RJ12 
connector of the sensor cable from the Control Unit (CU) 
to exit. See Wiring Diagram on Page 4. 
Make a small cut in the ceiling tile for the cable to exit. 
Step 4: Connect the RJ12 connector to the sensor 
bottom.
Step 5: Slide the Smart Sensor onto the screw head. 
Step 6: Slip the excess sensor cable up into the plenum 
area and adjust the ceiling tile to the original position.  
Step 7: Energize the luminaire and confirm that the 
green LED is solid.
Anchor Screw  
Sensor Cable
The Smart Sensor (SU-5S) should be mounted to the ceiling 
tile  within a few inches (between 1
3/4
” to 3”) of the lighting 
fixture. 
For wiring connections from the Control Unit to the sensor, 
refer to the Control Unit Installation Guide
Wiring Diagram:
LED Status
Description/Solution
LED not on
Check power and wiring
Green blinking
Sensor commissioned and working
Red blinking
Sensor not commissioned
Red solid
Faulty sensor – replace sensor
Green solid
Sensor installed, initialized, and uncommissioned 
– waiting for discovery.
Blue solid
Sensor received a request to identify itself  