4. Software Interfaces 
 
-31- 
Function/Setting 
Description 
Diagnostic 
 
Memory error 
 
Reverse energy 
 
Wrong writing 
 
Missing phase 
Accuracy @ 25
 
Current RMS Irms < 1.0% 
 
Voltage RMS Vrms < 1.0% 
 
Watt and Watt-hour < 1.0% 
 
Var and Var-hour < 2.0% 
 
4.1.2 Modbus 
commands 
The commands used in the Modbus register map are: 
 
Read holding register (0x03) 
 
Write multiple register (0x06) 
 
4.1.3  Modbus register map #1 
*NV: Non-volatile, V: Volatile, S: Signed, U: Unsigned, R: Read, W: Write 
Modbus 
Register 
Description 
Type/
Length
Storage 
Unit after 
Scaling 
Access 
Active Energy Consumption, Phase 1 MSW 
(valid) 
U32 NV 
Wh 
Active Energy Consumption, Phase 1 LSW 
U32 NV 
Wh 
Active Energy Consumption, Phase 2 MSW
U32 NV 
Wh 
Active Energy Consumption, Phase 2 LSW 
U32 NV 
Wh 
Active Energy Consumption, Phase 3 MSW
U32 NV 
Wh 
Active Energy Consumption, Phase 3 LSW 
U32 NV 
Wh 
Active Energy Consumption, Phase Sum 
MSW 
U32 NV 
Wh 
Active Energy Consumption, Phase Sum 
LSW 
U32 NV 
Wh 
Reactive Energy Consumption, Phase 1 
MSW(무효) 
U32 NV  VARh  R 
Reactive Energy Consumption, Phase 1 
LSW 
U32 NV  VARh  R