Simulcast Hardware Installation
Equipment Inspection and Inventory
Equipment Inspection and Inventory
Motorola recommends that an inventory of all equipment is taken with a Motorola representative to ensure
that the order is complete. Carefully inspect all equipment and accessories to verify they arrived in good
condition. Promptly report any damaged or missing items to a Motorola representative.
Placement Recommendations
The following are recommendations for placing equipment at a site:
Secure each rack on a firm, and level floor.
Use the correct mounting hardware to prevent rack movement.
Use strain relief when installing and positioning cables and cords to help
ensure that no interruption of service occurs.
Allow at least 1 m (3 ft.) of space at the front and rear of the system to allow for
proper air flow, cooling, and safe access to equipment. The system components
require an ambient air temperature of 0º C to 50º C (32º to 122º F).
Locate the site racks and other equipment with enough spacing to allow access for service.
Service personnel require access to both the front and rear of the racks.
Locate the system in an area that is free of dust, smoke, and electrostatic discharge (ESD).
Ground the racks according to the Standards and Guidelines for
Communication Sites (68P81089E50).
Spacing Requirements
Proper spacing of equipment is essential for ready access to equipment, ease of maintenance, and safety of
personnel. Spacing requirements have been established to meet the National Fire Protection Associations
(NFPA) Code, and the American Society of Heating, Refrigerating, and Air Conditioning Engineers
(ASHRAE) standards. Also, adhere to any local regulations that apply to spacing requirements.
See the Standards and Guidelines for Communication Sites (68P81089E50) for
details on these space requirements.
Weight Distribution Within a Rack
To avoid hazards or damage from uneven loading of a rack, distribute the weight of equipment
evenly in the rack, and consider the limitations of equipment and cables. When possible,
mount the heaviest components in the bottom of the rack.
68P81003Y71-O November 2002