Справочник Пользователя для Ever Sinline 1200VA/780W W/SL00TO-001K20/00

Модели
W/SL00TO-001K20/00
Скачать
Страница из 3
MODEL
Support time 
(100%/80%/50% Pmax)
Accumulator 
capacity
800VA/520W
1600VA/1040W 2000VA/1300W
~160 - 264V (~145 - 280V) ± 2%
45 - 55Hz  1Hz
± 
~184 - 264V (~167 - 280V) 
 
± 2%
~160V / 264V (~145V / 280V) 
 
± 2%
<3 ms
sinus
~230V ± 5%
50Hz   1Hz
±
LC
0 ms
2 x 12V 5Ah
3 x 12V 5Ah
5h
4 x PL
+ / -
RS 232
PowerSoft Personal
SINLINE 800
3)
UPS charging time 
190 x 165 x 480
14kg
sound and LED
1) For normal operation of the battery back-up the load connected to its output should not exceed 80% of value indicated in the table. Reserve power is essential to ensure continuous operation of 
connected devices in case of momentary rushes in load current.
2) User may modify the switching thresholds within the range provided. Default setting is provided in parentheses.
3) After discharging the UPS with 0.8 Pmax power – charging the battery to 90% capacity.
4) Continued exposure of the battery back-up to the ambient temperature exceeding +25°C will shorten the life of batteries.
5) If the altitude above sea level increases beyond the provided limit the permitted load power of the batter back-up decreases.
Rooms with low level of pollution
o
+10 C - +35 C / 
o
o
o
0 C - +45 C
up to 1000m
20 - 80% / 20 - 95% (
without condensation)
line-interactive (VI)
Tower
fuse
SINLINE 1200
SINLINE 1600
SINLINE 2000
1200VA/780W
2 x 12V 7Ah
7h
190x165x640
800, 1200, 1600, 2000, 3000
SINLINE
SINLINE 3000
3000VA/1950W
UPS
UPS + 
battery module
UPS
Battery module
UPS
UPS + 
battery module
UPS
Battery module
UPS
Battery module
-
-
-
4 x 12V 5Ah
4 x 12V 7Ah
5h
5h
7h
-
-
16kg
20kg
23kg
28kg
circuit breaker
W
a
rn
in
g
T
h
e
 m
a
n
u
fa
c
tu
re
re
s
e
rv
e
s
 t
h
e
 r
ig
h
to
 c
h
a
n
g
e
 t
h
e
 a
b
o
v
e
m
e
n
ti
o
n
e
d
 p
a
ra
m
e
te
rs
 w
it
h
o
u
n
o
ti
c
e
.
Output power (apparent/active)
1)
 
Input voltage 
2)
Range of output voltage 
2)
Shape of output voltage
BACK-UP (BATTERY) OPERATION MODE
Output voltage
Shape of output voltage
Switching thresholds: UPS – mains 
2)
Filtering of output voltage
Shorting safeguard
Frequency of output voltage
Frequency of input voltage
MAINS OPERATION MODE
Switching thresholds: mains - UPS 
2)
Time to switch to UPS
Overload protection
Filtering of output voltage
Technology
Case type
Switching time: UPS – mains
ENVIRONMENTAL PARAMETERS
Software
Number and type of outlet sockets
Telephone line / LAN filter
Communication interface
Signalling
Working environment
 
Operating / storage temperature 
4
)
 
Altitude above sea level
 
5
)
Relative humidity for operation / 
storage
EQUIPMENT
Overcurrent protection
MECHANICAL PARAMETERS
Dimensions in [mm] 
(h x w x d)
Weight
same as input but filtered
noise filter RFI-EMI varistor damper
Electronic
Electronic
5/7/12 min
4/5/8 min
4/5/9 min
4,5/6/10 min
3/4/8 min
~165V / ~259V (~150V / ~275V) ± 2%