11.0  MAKING CONNECTIONS TO THE X75
11.1  DC Load Connections
 
The DC load distribution connections at the rear left of the unit are clearly marked 
as follows:
11.1.1
  Circuit breaker option.
 
For each load circuit there are two terminals marked V1, V2, V3, V4 and V5 
respectively for the DC ‘feed’ and two marked RTN for the DC ‘return’.
11.1.2
  GMT Fuse option.
 
For each load circuit there is one terminal marked V1 through to V10 
respectively for the DC ‘feed’ and one marked RTN for the DC ‘return’.
 
Note that in the case of -48VDC system the ‘feed’ terminals are at a negative potential 
with respect to the ‘return’ terminals.  In the case of +24VDC and +12VDC systems 
the ‘feed’ terminals are at a positive potential with respect to the ‘return’ terminals.
 
When connecting to the DC load terminals it is important to ensure that the cables 
used are adequately sized to carry the expected load current for the circuit in question.
 
The maximum current rating for the individual load terminals is 32A, but where 
long cable runs to the load are expected care should be taken to avoid unacceptable 
cable voltage drop; this is most likely to occur at currents in excess of 20A if only a 
single feed and return cable are employed.  It is recommended that for circuits where 
a 20A or greater breaker is fitted pairs of feed and return cables are installed.
 
The terminals can accommodate wire sizes in the range #24AWG to #12AWG.
The table below gives recommended cable sizes for the available circuit capacities 
assuming semi-confined conditions.
Circuit Rating
Minimum Cable Size
½A , ¾A, 1A, 
1⅓A, 2A, 2½A 24AWG
3A, 5A
22AWG
10A. 12A
18AWG
15A
16AWG
20A
14AWG or 2 x 18AWG
25A, 30A
12AWG or 2 x 16AWG
Fi
gure 6 - Recommended Load Circuit Wire Sizes