Справочник Пользователя для innogy SE IEKA160

Скачать
Страница из 44
Technical Information 
LSX 
 
 
32 
4.4 
Display Elements 
The LEDs are on the front of the device. The function of the LEDs 1-4 is defined by 
the application. Each Ethernet port has a green and a yellow LED. 
LED 
Colour  Function 
off 
blinking  flashing  on 
Power 
green 
Supply 
missing 
 
 
 
LED 1-4 
 
depending 
on applica-
tion 
 
 
 
 
Ethernet 
LED 
green 
Link / Activ-
ity 
not con-
nected 
Data 
traffic 
 
connected 
yellow  Data rate 
10 Mbit/s 
 
 
100 Mbit/s 
Table 62: Meaning of the display elements 
4.5 
Reset key 
The functions soft reset and reset to default settings depend on the application. 
Designation 
Operation 
Meaning 
Reset 
Press at least 3 seconds. 
Resets the hardware and 
restarts it. 
(Hard reset) 
Press once for a short 
time. 
Resets the software and 
restarts it. 
(Soft reset) 
Press three times for a 
short time within 2 
seconds. 
Deletes all settings and 
resets the device to the 
factory defaults. 
Table 63: Function of the reset key