Листовка для Salicru SLC.1000.TWIN 618AA-10
Модели
618AA-10
(*) Spain only (**) R
est of W
orld
AVDA. DE LA SERRA 100 · 08460 PALAUTORDERA · SPAIN · FAX +34 93 848 11 51
REF. JM629B01 CODE 401AB000403 ED. JANUARY 2011
UNINTERRUPTIBLE POWER SUPPLY (UPS)
ASK FOR LOCAL
C O N D I T I O N S
YEARS
WA
RRANT
Y
MODEL
SLC TWIN 700 VA - 10kVA SLC TWIN/3 8 kVA - 20kVA
FORMAT
Tower or rack
(2)
Tower
TECHNOLOGY
On-line, double conversion, PFC, double DC bus
INPUT
Nominal voltage
220 / 230 / 240 V
(3)
3 x 380 / 400 / 415 V
Voltage range
176 ÷276 V
3 x 304 ÷ 478 V
Frequency
50 / 60 Hz
Frequency range
± 4 Hz
Power factor
≥ 0.98
(2)
≥ 0.95
Rectifier structure
PFC with Soft Start
OUTPUT
Nominal voltage
220 / 230 / 240 V
Voltage accuracy
±1% steady state; ±2% transient state
Maximum slew rate
1 Hz / s
Synchronisation
Mains present ± 4 Hz; free running ± 0.05 Hz
(2)
Efficiency
> 88% at full load
Total harmonic distortion (THDv)
≤
2% (linear load) ; ≤ 6% with non-linear load
(in accordance with EN 62040-3)
Permissible overloads
Up to 130% for 10 minutes; >130% for 1 second
Crest factor
3 to 1
BYPASS
Nominal voltage
220 / 230 / 240 V
Permissible voltage range
± 15%
Permissible frequency range
50 / 60 Hz ± 4 Hz
Overload
Up to 130% permanently; >130% for 1 second
BATTERIES
Battery type
Sealed, maintenance free
Protection
Against overvoltages, under voltages and alternating current component
CHARGER
Technology
PWM
Charge type
P/U (Constant power - Constant voltage)
Recharging time
7 hours up to 90%
8 hours up to 90%
COMMUNICA-
TION
TION
Ports
RS-232
Monitoring software
For platforms Windows, Linux and Mac
GENERALS
Operating temperature
0º C ÷ +40º C
Relative humidity
Up to 95%, non-condensing
Operating altitude
2400 m.a.s.l.
Acoustic noise level at 1metre
<45 dB
(2)
<60 dB
STANDARDS
Safety
EN 62040-1; EN 60950-1; EN 60529
Electromagnetic compatibility (EMC)
EN 62040-2
Operating
VFI in accordance with EN 62040-3
Marking
CE
Quality and environmental management
ISO 9001 and ISO 14001 TÜV
Extended autonomies.
(1)
Galvanic isolation.
(1)
Other input / output voltages.
(1)
Tower or 19” rack format.
Single or three-phase input.
Redundant parallel system ≥ 4 kVA.
Single or three-phase input.
Redundant parallel system ≥ 4 kVA.
RS-232 interface.
Monitoring software.
SNMP adapter / Web.
Monitoring software.
SNMP adapter / Web.
(1)
AS-400 card.
USB port card.
USB port card.
(1)
MODBUS protocol.
(1)
Temperature-humidity sensor.
(1)
AC input.
AC output.
Maintenance bypass.
RS-232 interface.
Intelligent slot (SNMP, USB, AS-400).
Data line protection RJ-11/RJ-45.
Battery module connection.
Input protection.
Parallel port.
AC output.
Maintenance bypass.
RS-232 interface.
Intelligent slot (SNMP, USB, AS-400).
Data line protection RJ-11/RJ-45.
Battery module connection.
Input protection.
Parallel port.
1.
2.
3.
4.
5.
6.
7.
8.
9.
2.
3.
4.
5.
6.
7.
8.
9.
Pre-sale and after sale advisory service.
Multiple formulae for maintenance and telemain-
tenance (SICRES).
Multiple formulae for maintenance and telemain-
tenance (SICRES).
TECHNICAL SPECIFICATIONS
SLC TWIN
ON-LINE DOUBLE CONVERSION UPS
700 VA - 20 kVA
700 VA - 20 kVA
DESCRIPTION
ADAPTABILITY
COMMUNICATIONS
SERVICES
TOWER MODEL
POWER
(VA / W)
DIMENSIONS
(D x W x H mm)
WEIGHT
(Kg)
INPUT/OUTPUT
SLC - 700 - TWIN
700 / 490
410 x 145 x 220
13
II / II
SLC - 1000 - TWIN
1000 / 700
410 x 145 x 220
14
II / II
SLC - 1500 - TWIN
1500 / 1050
470 x 195 x 347
30
II / II
SLC - 2000 - TWIN
2000 / 1400
470 x 195 x 347
31
II / II
SLC - 3000 - TWIN
3000 / 2100
470 x 195 x 347
32
II / II
SLC - 4000 - TWIN
4000 / 2800
575 x 260 x 717
84
II / II
SLC - 5000 - TWIN
5000 / 3500
575 x 260 x 717
87
II / II
SLC - 6000 - TWIN
6000 / 4200
575 x 260 x 717
90
II / II
SLC - 8000 - TWIN
8000 / 5600
575 x 260 x 717
92
II ó III / II
SLC - 10000 - TWIN
10000 / 7000
575 x 260 x 717
93
II ó III / II
SLC - 12000 - TWIN
12000 / 8400
575 x 260 x 717 (x 2)
48 + 131
III / II
SLC - 15000 - TWIN
15000 / 10500
575 x 260 x 717 (x 2)
49 + 131
III / II
SLC - 20000 - TWIN
20000 / 14000
575 x 260 x 717 (x 2)
50 + 131
III / II
RACK 19” MODEL
POWER
(VA / W)
DIMENSIONS
(D x W x H mm)
WEIGHT
(Kg)
INPUT/OUTPUT
SLC - 700 - TWIN R
700 / 490
450 x 483 x 87 (2U)
16
II / II
SLC - 1000 - TWIN R
1000 / 700
450 x 483 x 87 (2U)
17
II / II
SLC - 1500 - TWIN R
1500 / 1050
450 x 483 x 87 (2U) (x 2)
10 + 28
II / II
SLC - 2000 - TWIN R
2000 / 1400
450 x 483 x 87 (2U) (x 2)
11 + 28
II / II
SLC - 3000 - TWIN R
3000 / 2100
450 x 483 x 87 (2U) (x 2)
12 + 28
II / II
SLC - 4000 - TWIN R
4000 / 2800
600 x 483 x 132 (3U) (x 2)
14 + 64
II / II
SLC - 5000 - TWIN R
5000 / 3500
600 x 483 x 132 (3U) (x 2)
14.5 + 64
II / II
SLC - 6000 - TWIN R
6000 / 4200
600 x 483 x 132 (3U) (x 2)
15 + 64
II / II
RANGE
(2) Depending on the model (3) Voltage availability of 110 / 115 / 120 / 127 V (4) On line mode
Values for standard autonomies. For other configurations, consult dimensions and weights.
Data may change without previous notice.
(1) Optional
1 kVA rack model
2 kVA tower model
6 kVA tower model