1. Purpose 
This specification defines the performance characteristics and functions of a 500 watts redundant power 
supply with Active PFC (Power Factor Correction) and hot swappable capabilities.   
 
2. AC Input Requirements 
!
2.1 Input 
Voltage 
and 
Frequency 
Voltage (sinusoidal) : 100~240 VAC full range, with  10% tolerance. Input frequency ranges from 
47hz~63hz 
 
2.2  AC Input Current and Inrush Current 
AC line inrush current shall not damage any component nor cause the AC line fuse to blow under any 
DC conditions and with any specified AC line input voltage and frequency. Repetitive On/Off cycling of 
the AC input voltage shall not damage the power supply.
 
 
Table 1: AC Input Current and Inrush Current 
Input 
Voltage 
Input Current 
Maximum 
Inrush Current 
100~240Vac 10% 
7A ~3.5A 
50Apeak@115VAC 
 
2.3    Input Power Factor Correction (Active PFC) 
The power factor at 100% of rated load shall be 
≥ 0.95 at nominal input voltage.
 
 
2.4  AC Line Transient Specification 
AC line transient conditions are characterized as “sag” and “surge” conditions. Sag conditions (also referred 
to as “brownout” conditions) will be defined as the AC line voltage dropping below nominal voltage. Surge 
conditions will be defined as the AC line voltage rising above nominal voltage. The power supply shall meet 
the regulation requirements under the following AC line sage and surge conditions. 
Table 2: AC Line Sag Transient Performance 
Duration Sag 
Operating 
AC 
Voltage Line 
Frequency 
Load Performance 
Criteria 
Continuous 
10% 
Nominal AC Input ranges 
50/60 Hz 
100% 
No loss of function or 
performance  
0-1 AC cycle
100% 
Nominal AC Input ranges 
50/60 Hz 
80% 
No loss of function or 
performance  
> 1 AC cycle 
> 10% 
Nominal AC Input ranges 
50/60 Hz 
100% 
Loss of function Acceptable 
 
 
Table 3:    AC Line Surge Transient Performance