Справочник Пользователя для Toshiba VF-AS1

Скачать
Страница из 326
!
  E6581301!
G-3 
3) Connection with transistor output 
!
The inverter can be controlled by connecting 
the input terminal with output (contactless 
switch) of a programmable controller. Use 
this function to specify forward/reverse run or 
a preset speed operation. Use a transistor 
that operates on 24Vdc, 5mA power.
CC
Input terminal 
  Inverter   
  Programmable controller   
* Interface between programmable controller and inverter 
When using an open-collector output type programmable control device to control the operation of a motor, connect 
cables, as shown in the schematic diagram for sink/source logic (when an external power supply is used) on page 
B-15. When using the internal power supply of the inverter, connect cables, as shown in the schematic diagram on 
page B-14. If the programmable control device is turned off with the inverter left on, an incorrect signal will flow into 
the inverter, as shown in the figure below, because there is a potential difference between the control power 
supplies. Be sure to provide an interlock so that the programmable controller cannot be turned off when the inverter 
is on. 
External +24V 
power supply 
P24 
COM 
Fuse 
Fuse blowout 
detector circuit 
Inverter internal 
+24V power 
supply 
+24V 
Programmable controller   
Inverter 
Input terminal 
(F, R, ST….) 
■ Example of use- three-wire operation (SW1 set to sink logic) 
The three-wire operation function allows you to make the inverter self-hold its operation, without setting up a 
sequential circuit, so that the inverter can be operated by means of external signals (reset contact signals). 
CC 
S3 
Reverse run 
HD   
Forward run (F): 
If you press the Forward (F) button, the 
motor rotates in the forward direction at the 
frequency specified with a command. 
Reverse run (R): 
If you press the Reverse (R) button, the 
motor rotates in the reverse direction at the 
frequency specified with a command. 
HD (S3): 
If you press the HD (S3) button, the motor 
decelerates and comes to a stop.
R
Forward run 
[Parameter setting] 
Terminal 
symbol 
Title 
Function 
Adjustment range
Example of setting 
S3 
H
Input terminal function 
selection 7(S3)
"
( HD operation retention)