TECHNICAL SPECIFICATIONS
Input
Input Voltage
48 VDC
Inrush Current
0.20 A (peak cold start)
Hold-Up Time
20 msec minimum at full load and nominal input
voltage
voltage
Isolation Voltage
(Dielectric withstand) Meets IEC 960 for one minute.
1,500 VAC:
Output/Input
500 VAC:
Input/Safety GND
500 VAC:
Output/Safety GND
Output
Output Voltage
12 VDC
Output Current
0.8 A
Line Regulation
±0.5 % of all output within specified range
Load Regulation
±1.0 % at 20 % load to full-rated load
Cross Regulation
±1.0 % maximum on any output change from 50 % to
100 % rated load
100 % rated load
Transient Response
Output voltage returns in less than 3 msec following a
50 % load change
50 % load change
Over Load Protection
(OLP) When the average power rating exceeds 125%-
150% of maximum power, output voltages reduced to
a safe dissipation level; protects against short circuit of
any output.
150% of maximum power, output voltages reduced to
a safe dissipation level; protects against short circuit of
any output.
Over Voltage Protection (OVP) 124 % ±8 % on output.
Over Circuit Protection Withstands a continous short without damage; returns
automatically to regulation upon removal of short.
No Load Operation
No damage to power supply when operating at no
load.
load.
Overshoot Protection
No voltage spike at power-on, power-off, or power
failure.
failure.
4.
Connect +48-VDC terminal to 48-to-12 VDC External Power Supply
terminal block control marked “+”. Turn terminal screw clockwise to
secure.
terminal block control marked “+”. Turn terminal screw clockwise to
secure.
5.
Connect -48-VDC terminal to 48-to-12 VDC External Power Supply
terminal block control marked “-”. Turn terminal screw clockwise to
secure.
terminal block control marked “-”. Turn terminal screw clockwise to
secure.
6.
Connect ground terminal to 48-to-12 VDC External Power Supply
terminal block control marked “chassis ground”. Turn terminal screw
clockwise to secure.
terminal block control marked “chassis ground”. Turn terminal screw
clockwise to secure.
7.
Ensure that external power source is powered ON.
GND
-
+