Справочник Пользователя для IBM UPS 10000XHV 21308RX

Модели
21308RX
Скачать
Страница из 4
Rail set, accessory kit, UPS serial cable, UPS cable, EPO cable, four rack jumper cords,  documentation and
software CDs.
Ship group components
FCC, UL 1778, CSA C22.2 Number 950, NOM, CE-Mark (EN55022 Class A), C-Tick Mark (AS/NZS 3548
Class A), VDE EN50091-1-1 and 60950
Approvals
IBM 
^
TM
 xSeries 
®
 Rack Configurator at ibm.com/pc/us/eserver/xseries/library/configtools.html
Configuration aid
Temp: 0-40C (32-104F)
Relative humidity: 0-95%
Altitude (max): 3000m (10,000ft)
Environmental
Emergency power off, optional UPS Extend Run external battery packs, hot-swap batteries, integrated
network management, intelligent battery management, overload indicator, rack mount, replace-battery
indicator, resettable circuit breaker, status indicator LEDs
General features
3-year limited onsite warranty
Warranty
1
Black
Color
267 x 430 x 685 mm
(16.5x23.5x36.6in)
Dimensions (HxWxD)
109kg (240 lbs), 118kg (260lbs) Shipping
Weight
• Internal battery provides approximately seven minutes of run time at a load of 6000W 
• Supports up to four Extend Run Battery Packs for up to 37 additional minutes of run time
Battery backup times
Microsoft
®
 Windows 2003
®
 4.0, Windows
®
 2000, Windows XP, Novell NetWare 6.0, Red Hat Linux
TM
 7.3
 
Software support
PowerChute Business Edition for IBM, PowerChute Network Shutdown for IBM
Software included
• 4 IEC 320-C19, individually breakered
Outlets
USB, serial, and 10/100 baseT Network card
Connections for
management
• On line: 96%; On battery: 98%
Efficiency
47-63Hz (auto adjusting)
Input frequency
• None - must be hard wired directly into room power supply
Input inlet/Current
200V; 208V; 220V; 230V; 240V
Current 50 A single phase; 18 A / phase three phase when on-line, 50A on L1 when in bypass
Rated output
6U rack-mountable
Form Factor
21308RX
Part number
UPS10000XHV
Model
IBM UPS10000X at a glance
3