Справочник Пользователя для Brainboxes ED-527

Скачать
Страница из 8
+44(0) 151 220 2500  sales@brainboxes.com  www.brainboxes.com
ED-527 Ethernet 16 DO
Browser Interface
 Webserver Interface
Configure IP address, monitor state of i/o lines, set the Watchdog Timers Output Reset Value, Set Power on digital output 
value
 Programming Interface
No device driver needed, just open a TCP connection and send simple ASCII commands.
Software drivers give local COM Port interface for configuration
 Utility Programs
Find device, configure IP address
102 mm
128 mm
22.6 mm
Type of Port Terminal 
Block
Pin 1
Pin 2
Pin 3
Pin 4
Pin 5
Digital Out
Yellow
GND
DOut  0
DOut 1
DOut 2
DOut 3
Digital Out
Orange
GND
DOut 4
DOut 5
DOut 6
DOut 7
Gateway
Grey
GND
RS-485 D- RS-485 D+ RS-485 D+ RS-485 D-
Digital Out
Green
GND
DOut 8
DOut 9
DOut 10
DOut 11
Digital Out
Blue
GND
DOut 12
DOut 13
DOut 14
DOut 15
Power
Black 
Power GND
+Vin A
+Vin B
Power GND Func GND
Link LED
Status LED
Activity LED
Gateway LED
Reset Hole
Ethernet Port
Housing
IP-20 rated non-conducting polyamide case with integrated DIN rail mount
Watchdog
Power up
On power up all outputs go to user programmable power on known good state
Watchdog coms link
On loss of communications link all outputs go to a user programmable watchdog comms known good state. 
Watchdog hardware timer
If the firmware does not refresh the watchdog timer within a predetermined interval then all outputs go to a user 
programmable watchdog hardware good state 
Ethernet
 Ethernet Port
1 x RJ45 jack, 10/100Mhz autosensing, crossover auto sensing (Auto MDIX)
 Protection
1,500Volts magnetic isolation between I/O ports and network
 Network Protocols
ICMP, IP, TCP, DHCP, Telnet, HTTP
 Connection to Network
Ethernet 10BaseT / 100BaseTX