Справочник Пользователя для Hitachi RAF-25PXA RAF25PXA
Модели
RAF25PXA
10-29
5. Installation of indoor unit
Set nut and washer on suspension bolt and hook it to
suspend clamp by lifting the indoor unit.
Make sure that indoor unit is kept level using a level or vinyl
hose with water.
Fix the indoor unit so that the space between bottom
surfaces of ceiling and indoor unit is 58mm.
Set nut and washer on suspension bolt and hook it to
suspend clamp by lifting the indoor unit.
Make sure that indoor unit is kept level using a level or vinyl
hose with water.
Fix the indoor unit so that the space between bottom
surfaces of ceiling and indoor unit is 58mm.
CAUTION
•
Be sure to install the indoor unit level. If the
indoor unit is inclined, water may leak.
indoor unit is inclined, water may leak.
•
If the space between bottom surfaces of indoor
unit and ceiling is not correct, there may be a
gap between the grille and ceiling surface, which
will cause dripping of condensed water.
unit and ceiling is not correct, there may be a
gap between the grille and ceiling surface, which
will cause dripping of condensed water.
INSTALLATION OF NON DUCT TYPE
Non duct type
Need optional parts when install non duct type
①
①
Discharge grille
②
Discharge duct
③
Suction grille
1. Installation figure
•
Select the indoor unit position, fixing direction of air
outlet so that cool/hot air reaches all the room.
outlet so that cool/hot air reaches all the room.
Indoor unit
Filter
Filter holders
Back plate
(1) Bottom side suction opening
Indoor unit
Back plate
(2) Back side suction opening
Opening on ceiling 960
Suspension bolt 790
10
890
30
10
140
Discharge duct
Indoor unit
200
10
347
520
10
Ope
nin
g o
n c
eiling
5
20
S
us
pe
ns
ion b
olt
3
47
Discharge grille
Suction grille
Above 300
Above 300
97
164
45
45
980
540
52
A
b
o
ve 650
A level
Ceiling
58mm
Suspension bolt (M10)
(Local purcahase)
Washer
(Local purchase)
Hexagon nut (M10)
(Local purchase)