Справочник Пользователя для Hitachi RAC-25FXA RAC25FXA

Модели
RAC25FXA
Скачать
Страница из 706
 
10-34
 
 
10.1.6  INSTALLATION OF MIDDLE STATIC 
PRESSURE DUCT TYPE INDOOR 
 
Please read the safety precautions carefully before 
operating the unit. The contents of this section are vital to 
ensure safety. Please pay special attention to the following 
signs. 
WARNING  Incorrect methods of installation may 
cause death or serious injury 
CAUTION   Improper installation may result in 
serious consequences. 
 Make sure to connect earth wire 
 This sign indicates prohibition 
Be sure that the unit operates in proper condition after 
installation. Explain to customer the proper way of 
operating the unit as described in the user’s guide. 
 WARNING 
• 
Please request your sales agent or qualified 
technician to install your unit. Water  leakage, short 
circuit of fire may occur if you do the installation 
work yourself. 
• 
Please observe the instructions stated in the 
installation manual during the process of 
installation. Improper installation may cause water 
leakage, electric shock and fire. 
• 
Make sure that the units are mounted at locations 
which are able to provide full support of the weight 
of the units. If not, the units may collapse and 
impose danger. 
• 
Observe the rules and regulations of the electrical 
installation and the methods described in the 
installation manual when dealing with the electrical 
work. Use power cables approved by the authorities 
of your country. 
• 
Be sure to use the specified wire for connecting the 
indoor and outdoor units. Please ensure that the 
connections are tight after the conductors of the 
wire are inserted into the terminals. Improper 
insertion and loose contact may cause over-heating 
and fire. 
• 
Please use the specified piping set for the correct 
refrigerant gas. Otherwise, this may result in broken 
copper pipes or faults 
• 
When installing or removing an air conditioner, don 
not allow air or moisture to remain in the 
refrigeration cycle. Otherwise, pressure in the 
refrigeration cycle may become abnormally high 
may cause a rupture. 
• 
Be sure to ventilate fully in case refrigerant gas 
leaks while at work. If the refrigerant gas comes into 
contact with fire, poisonous gas might be 
discharged. 
• 
After completion of installation work, check to make 
sure that there is no refrigeration gas leakage. If the 
refrigerant gas leaks into the room, coming into 
contact with fire in a fan-driver heater, space heater, 
etc; poisonous gas may be emitted. 
• 
Unauthorized modifications to the air conditioner 
may be dangerous. If a breakdown occurs, please 
contact a qualified air conditioner technical or 
electrician. Improper repairs may result in water 
leakage, electric shock and fire. 
• 
Be sure to connect the earth wire from power 
supply wire to the outdoor unit and between the 
outdoor and indoor unit. Improper grounding may 
cause electric shock. 
 
 
 
 CAUTION 
• 
A circuit breaker or fuse must be installed. Without 
a circuit breaker or fuse, the danger of electric 
shock exists. A main switch with a contact gap of 
more than 3.5mm has to be installed in the power 
supply line to the outdoor unit. 
• 
Do not install the unit near a location where there is 
a flammable gas. The indoor unit may catch fire if 
flammable gas leaks around it. 
• 
Be sure to tighten the  flare nut to the specified 
torque using a toque wrench. If the flare nut is 
tightened excessively, it may crack as time elapses, 
causing the refrigerant leakage. 
• 
Please ensure smooth flow of water when installing 
the drain hose. 
• 
Piping shall be suitable supported with a maximum 
spacing of 1m between supports 
• 
An IEC approved power cord should be used. 
Power cord type: NYM. 
• 
“Height difference“ and “Piping length” of Indoor and 
Outdoor unit differs depending on  the Outdoor unit. 
Please refer to the “Installation manual” in Outdoor 
unit 
 
 
Proper place for Installation 
 
Indoor unit 
Refrigerating pipes can be drawn from the back, the under 
the left side of the indoor unit. In the case that refrigerating 
pipes are drawn form the left side, confirm the smooth 
flowing of condensed water. If not, the condensed water 
will overflow into the room. When the pipes are drawn from 
the right or left side, the pipes can be connected easily by 
configuration the pipes before installation. 
 
 
Be sure to 
completely seal 
any gap with 
putty. 
The indoor piping 
should be 
insulated with the 
enclosed 
insulation pipe. (If 
the insulator is 
insufficient, please 
use commerical 
porducts 
Adiabated pipes 
must always be 
used for both 
large and small 
diameter. Wrap 
pipes with tape. 
An adiabator will 
weather 
excessively if not 
tape-wrapped. 
Drain pipe must be installed 
separately. Insulate indoor part of 
pipe to prevent condensation