Testing Contactors (Starters) 
1.
 
Press 
D
 to select emissivity. Press 
A
 to select LO for bright contacts, or MED for darkened 
contacts. 
2.
 
Press 
C
and the press 
A
 to select MAX. 
3.
 
Measure line and load side of one pole without releasing trigger. 
4.
 
A temperature difference between the line and load sides of a pole indicate increased resistance of 
one point and a contactor may be failing. 
Testing Enclosed Relays 
1.
 
Press 
D
 and then press 
A
 to set emissivity to LO for uninsulated connectors or HI for plastic 
encased relays or for bakelite enclosed relays or insulated connectors. 
2.
 
Press 
C
 and then press
 
A
 to select MAX. 
3.
 
Start the scan. 
4.
 
Measure the relay casing, looking for hot spots. 
5.
 
Measure electrical connections on relay terminals looking for hot spots. 
Testing Fuses and Buss Connections 
1.
 
Press 
D
 and then press 
A
 to set emissivity to HI for paper covered fuse body or insulated 
connections. 
2.
 
Press 
C
 and then press 
A
 to select MAX. 
3.
 
Scan the paper covered length of fuse. 
4.
 
Without releasing the trigger, scan each fuse. Unequal temperatures between fuses may indicate 
voltage or amperage imbalance. 
5.
 
Press 
D
 and then press 
A
 to select LO, for metal fuses end caps and uninsulated buss 
connections. 
6.
 
Press 
C
 and then press 
A
 to select MAX. 
7.
 
Scan each end cap on each fuse. 
Note 
Unequal temperatures or a high temperature indicates loose or corroded connection through 
the fuse buss spring clip. 
Testing Electrical Connections 
1.
 
Press 
D
 and then press 
A
 to select LO emissivity for uninsulated connectors or buss 
connections or HI for insulated connections. 
Note 
Conductors are typically smaller than the Thermometer’s spot size. If the spot size is bigger 
than the connector, the temperature reading is the average within the spot. 
2.
 
Scan the conductor, moving toward direction of electrical connector (quick connect, wire nut, buss 
connection, or lug).