Fig. 5.36: Phase sequence test menu
Connect the test cable to the BENNING IT 110/ BENNING IT 120 B
Step 2
Follow the connection diagram shown in figure 5.37 to test phase sequence.
L3
L2
L1
N
PE
N
/L
2
N
/L
2
L/
L1
L/
L1
P
E
/L
3
P
E
/L
3
result 1.2.3
option
result 2.1.3
Fig. 5.37: Connection of universal test cable and optional three phase cable
Step 3
Check the displayed warnings and online voltage/terminal monitor. Continuous test is
running. The actual result is shown on the display during the test. All three-phase volta-
ges are displayed in order of their sequence represented by the numbers 1, 2 and 3.
running. The actual result is shown on the display during the test. All three-phase volta-
ges are displayed in order of their sequence represented by the numbers 1, 2 and 3.
Fig. 5.38: Example of phase sequence test result
Displayed result:
Ph
Ph
Phase sequence
1.2.3
Correct connection (clockwise phase rotation)
2.3.1
Wrong connection (anticlockwise phase rotation)
-.-.-
Irregular voltages
Save displayed results for documentation purposes. Refer to chapter 6.1 for further information on
setting functions and saving of measurement results (BENNING IT 120 B only).
setting functions and saving of measurement results (BENNING IT 120 B only).
5.7 Voltage and frequency (V~)
How to perform voltage and frequency measurement:
Step 1
Step 1
Select VOLTAGE V~ function with the function selector switch. The following menu is
displayed:
displayed: